Bus Duct Cooling Flashcards

1
Q

What are the Bus Duct Fan auto starts?

A
  • Low Flow (5” H2O decreasing) with C/S in auto
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What cools the Bus Duct

A
  • TACW
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What has to be done if both Bus Duct fans fail?

A
  • bus loading must be reduced to a maximum of 10,000 amps per phase (approx. 38-40% power)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Which unit has the Deionizing Baffle and what is it for?

A
  • Unit 1 and they prevent transferring ionized air (arcing) from one phase to another (they are between the main transformer connections)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the bus duct flow path for U1?

A
  1. Cooler
  2. Fan
  3. Supply Via Middle Duct
  4. Deionizing baffles
  5. Return in North and South ducts
  6. Interplenum
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the bus duct flow path for U2?

A
  1. Cooler
  2. Fan
  3. Out South duct to generator terminals
  4. MT Dampers
  5. Return in North and middle ducts
  6. Interplenum
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many Bus Duct Cooling Fans do we need to operate at 100% power?

A
  • 1 Bus Duct Cooling fan needed for 100% operation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the Max Design Temp of bus ducts?

A
  • Maximum design temp is 180°F (82.2°C)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly