Bus Duct Cooling Flashcards
1
Q
What are the Bus Duct Fan auto starts?
A
- Low Flow (5” H2O decreasing) with C/S in auto
2
Q
What cools the Bus Duct
A
- TACW
3
Q
What has to be done if both Bus Duct fans fail?
A
- bus loading must be reduced to a maximum of 10,000 amps per phase (approx. 38-40% power)
4
Q
Which unit has the Deionizing Baffle and what is it for?
A
- Unit 1 and they prevent transferring ionized air (arcing) from one phase to another (they are between the main transformer connections)
5
Q
What is the bus duct flow path for U1?
A
- Cooler
- Fan
- Supply Via Middle Duct
- Deionizing baffles
- Return in North and South ducts
- Interplenum
6
Q
What is the bus duct flow path for U2?
A
- Cooler
- Fan
- Out South duct to generator terminals
- MT Dampers
- Return in North and middle ducts
- Interplenum
7
Q
How many Bus Duct Cooling Fans do we need to operate at 100% power?
A
- 1 Bus Duct Cooling fan needed for 100% operation
8
Q
What is the Max Design Temp of bus ducts?
A
- Maximum design temp is 180°F (82.2°C)