Book 2 Chapter 26: Refrigeration & AC System Controls Flashcards
Why must you avoid running a refrigeration system below 14kPa when pumping down?
A) A slightly positive system pressure is required to prevent air infiltration
B) Too much refrigerant will be required for a recharge
C) The compressor will need to be stopped to prevent it running dry
D) The system heat exchangers will ice up
A) A slightly positive system pressure is required to prevent air filtration
What is the purpose of the chilled water flow switch?
A) Starts the compressor on a low refrigerant flow condition
B) Opens the vanes so that the compressor can be restarted under load
C) Protects the chiller from freezing due to lack of water flow
D) Starts the chilled water booster pump
C) Protects the chiller from freezing due to lack of water flow
Where can refrigeration system log sheets be obtained from?
A) Refrigeration system manufacturers
B) Inspection and insurance companies
C) Developed by the refrigeration system operator
D) All of the above
D) All of the above
Which of the following is not a benefit of a preventive maintenance program?
A) Control of labour and material costs
B) Allows for the accumulation of all spare parts for each piece of equipment in case of a major breakdown
C) Accumulation of history records for each piece of equipment
D) Better means of identifying causes of breakdowns
B) Allows for the accumulation of all spare parts for each piece of equipment in case of a major breakdown
What is the symptom of a refrigeration system that has high suction pressure due to an oversized expansion valve?
A) An abnormally cold suction line
B) Undersized compressor
C) Fouled condenser
D) Contaminants in the refrigerant
A) An abnormally cold suction line
The safety control on a centrifugal compressor that ensures the compressor will only be started under a no-load condition is called what?
A) Low oil pressure cutout switch
B) Motor demand limiter
C) Vane closed switch
D) Chilled water flow switch
E) Condenser high pressure cutout
C) Vane closed switch
Which of the following code books deals with refrigeration systems?
A) CSA B52
B) CSA B51
C) ASME Section VII
D) ASNI
E) ASME Section IV
A) CSA B52
Before starting a compression refrigeration system:
A) Ensure that compressor oil level and temperature is within specification
B) Open the condenser fan breakers
C) Make sure recycle timer is engaged
D) Shut off engine room fans
E) Close louvres to engine room air make up units
A) Ensure that compressor oil level and temperature is within specification
Which of the following steps is not part of the start-up procedure of centrifugal compressor refrigerating system?
A) Operate the oil pump for at least 10 minutes before starting the compressor
B) Open the main circuit breakers
C) Open the makeup water valve
D) Open the stop valves in the chilled water system
E) Check the refrigerant levels
B) Open the main circuit breakers
Refrigeration systems:
A) Require operators to be familiar with the system
B) Do not require supervision
C) Start automatically and need no operator input
D) Will shutdown automatically if there is a problem
E) Are standard and operated in similar ways
A) Require operators to be familiar with the system
When some refrigeration systems are to be shutdown for a prolonged period of time they should be “pumped down” and the refrigerant stored in the:
A) Accumulator
B) Compressor
C) Receiver
D) Evaporator
E) Supply cylinders
C) Receiver
When starting a compression refrigeration system after ensuring that all components and auxiliaries are properly energized:
A) Check the pressure cutouts and interlocks
B) Open the suction
C) Shut the king valve
D) Push the start button
E) Close the water supply to the condenser
A) Check the pressure cutouts and interlocks
Before starting a compression refrigeration system:
A) Close the expansion valves
B) Close the compressor discharge
C) Bleed the discharge check valve
D) Close the king valve
E) Check compressor oil
E) Check compressor oil
If the compressor suction pressure is too high it may be due to:
A) Expansion valve is struck open
B) Broken compressor suction valves
C) Too much load on the evaporator
D) All of the above
E) None of the above
D) All of the above
A system of regularly scheduled inspections and lubrications along with the adjustments, minor parts replacement and minor repairs necessary to keep the refrigerating plant and equipment in good operating condition is defined as what:
A) Routine operation
B) Safety controls
C) Regular maintenance
D) Preventative maintenance
E) None of the above
D) Preventative maintenance