Book 1 Chapter 8: Heating Boiler Operating Controls Flashcards
The burner control that continually adjusts the firing rate to maintain the boiler pressure at a constant value is called _________.
A) on-off
B) high-low
C) modulating
D) high limit
C) modulating
The name of the second spring that is used to increase the span between cut-in cut-out is the ____________ control.
A) differential
B) high-low
C) mid spring
D) set point
A) differential
The simplest type of burner operating control used on low capacity boilers is the ___________.
A) modulating
B) high-low
C) high limit
D) on-off
D) on-off
The device used on hot water boilers to maintain the water temperature is the _________.
A) immersion bulb
B) bellows
C) modulator
D) aquastat
D) aquastat
The name of the switch used to start or stop the boiler is the _________ switch.
A) selector
B) burner
C) flame control
D) high-low
B) burner
If the low air pressure switch is activated it will close the _________.
A) damper
B) main fuel valve
C) pilot gas valve
D) feedwater valve
B) main fuel valve
The cut-out pressure setting for a high pressure safety control used to protect a low-pressure steam boiler will be:
A) 103 kPa
B) lower than the cut-out pressure of the operating control
C) just below the popping pressure
D) no higher than 200 kPa
C) just below the popping pressure
A manual “high-low” switch should be switched to “high” or “auto”:
A) Prior to ignition of the main flame
B) When the pressure is too low
C) As soon as the main flame has stabilized
D) During the boiler pre-purge
E) When the boiler has been properly warmed up
E) When the boiler has been properly warmed up
A levelling indicator is found on:
A) A low water fuel cut-off switch
B) An on-off pressure control switch
C) The casing of a heating boiler
D) A modutrol motor
E) A boiler feedwater pump
B) An on-off pressure control switch
In a hot water heating system, the water temperature must never exceed:
A) 121C
B) 100C
C) 80C
D) 110C
E) 60C
A) 121C
Quickly closing the main burner manual cock valve during boiler operation should check the:
A) Flame Scanner
B) High gas pressure fuel cut-off
C) Combustion air proving switch
D) Low gas pressure fuel cut-off
E) Low fire interlock switch
B) High gas pressure fuel cut-off
Code requirement maximum setting for a high limit control on a steam heating is:
A) 68.9 kPa (10psi)
B) 103 kPa (15psi)
C) 862 kPa (125psi)
D) 207 kPa (30psi)
E) 35 kPa (5psi)
B) 103 kPa (15psi)
Modulating burner controls operate by regulating:
A) Steam flow and fuel flow
B) Fuel flow, air flow, and feedwater pressure
C) Fuel temperature and air flow
D) Fuel flow and air flow
E) Fuel flow and atomizing steam flow
D) Fuel flow and air flow
The high steam pressure fuel cut-off:
1. Requires an isolation valve for maintenance
2. Is exposed to boiler steam
3. Requires a water seal between it and the boiler
4. Needs to be reset after each operation
A) 1,2
B) 2,3
C) 1,2,3,4
D) 2,3,4
E) 3,4
E) 3,4
A high limit control switch:
A) Must be used when a boiler is not under continuous supervision
B) Usually does not require manual resetting
C) Is a normally open switch
D) Is necessary on all boilers
E) Activates after the safety valve opens
A) Must be used when a boiler is not under continuous supervision