Book 1 Chapter 8: Heating Boiler Operating Controls Flashcards

1
Q

The burner control that continually adjusts the firing rate to maintain the boiler pressure at a constant value is called _________.
A) on-off
B) high-low
C) modulating
D) high limit

A

C) modulating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The name of the second spring that is used to increase the span between cut-in cut-out is the ____________ control.
A) differential
B) high-low
C) mid spring
D) set point

A

A) differential

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The simplest type of burner operating control used on low capacity boilers is the ___________.
A) modulating
B) high-low
C) high limit
D) on-off

A

D) on-off

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The device used on hot water boilers to maintain the water temperature is the _________.
A) immersion bulb
B) bellows
C) modulator
D) aquastat

A

D) aquastat

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The name of the switch used to start or stop the boiler is the _________ switch.
A) selector
B) burner
C) flame control
D) high-low

A

B) burner

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

If the low air pressure switch is activated it will close the _________.
A) damper
B) main fuel valve
C) pilot gas valve
D) feedwater valve

A

B) main fuel valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The cut-out pressure setting for a high pressure safety control used to protect a low-pressure steam boiler will be:
A) 103 kPa
B) lower than the cut-out pressure of the operating control
C) just below the popping pressure
D) no higher than 200 kPa

A

C) just below the popping pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A manual “high-low” switch should be switched to “high” or “auto”:
A) Prior to ignition of the main flame
B) When the pressure is too low
C) As soon as the main flame has stabilized
D) During the boiler pre-purge
E) When the boiler has been properly warmed up

A

E) When the boiler has been properly warmed up

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

A levelling indicator is found on:
A) A low water fuel cut-off switch
B) An on-off pressure control switch
C) The casing of a heating boiler
D) A modutrol motor
E) A boiler feedwater pump

A

B) An on-off pressure control switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In a hot water heating system, the water temperature must never exceed:
A) 121C
B) 100C
C) 80C
D) 110C
E) 60C

A

A) 121C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Quickly closing the main burner manual cock valve during boiler operation should check the:
A) Flame Scanner
B) High gas pressure fuel cut-off
C) Combustion air proving switch
D) Low gas pressure fuel cut-off
E) Low fire interlock switch

A

B) High gas pressure fuel cut-off

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Code requirement maximum setting for a high limit control on a steam heating is:
A) 68.9 kPa (10psi)
B) 103 kPa (15psi)
C) 862 kPa (125psi)
D) 207 kPa (30psi)
E) 35 kPa (5psi)

A

B) 103 kPa (15psi)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Modulating burner controls operate by regulating:
A) Steam flow and fuel flow
B) Fuel flow, air flow, and feedwater pressure
C) Fuel temperature and air flow
D) Fuel flow and air flow
E) Fuel flow and atomizing steam flow

A

D) Fuel flow and air flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The high steam pressure fuel cut-off:
1. Requires an isolation valve for maintenance
2. Is exposed to boiler steam
3. Requires a water seal between it and the boiler
4. Needs to be reset after each operation

A) 1,2
B) 2,3
C) 1,2,3,4
D) 2,3,4
E) 3,4

A

E) 3,4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A high limit control switch:
A) Must be used when a boiler is not under continuous supervision
B) Usually does not require manual resetting
C) Is a normally open switch
D) Is necessary on all boilers
E) Activates after the safety valve opens

A

A) Must be used when a boiler is not under continuous supervision

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The main concern of the boiler operator is to operate a boiler:
A) With the water level as high as possible
B) As quietly as possible
C) Without need for water treatment
D) As economically as possible
E) As safely and as efficiently as possible

A

E) As safely and as efficiently as possible

17
Q

An on-off steam boiler:
A) Cannot operate in a multi-boiler system
B) Will cycle on and off based on a regular timed cycle
C) Must have a low capacity
D) Will maintain a fairly constant steam pressure
E) Operates most efficiently at continuous firing

A

E) Operates most efficiently at continuous firing

18
Q

A high gas pressure fuel cut-off switch:
A) Must be located upstream of an automatic
B) Is a normally open switch
C) Closes when gas pressure is too high
D) Opens when gas pressure is too high
E) Is never a manual reset device

A

D) Opens when gas pressure is too high

19
Q

Ideally, the cut out pressure of the high limit control of a steam heating boiler should not exceed:
A) 95% of the safety valve setting
B) 90% of the safety valve setting
C) 100% of the safety valve setting
D) 75% of the safety valve setting
E) 80% of the safety valve setting

A

B) 90% of the safety valve setting

20
Q

A safeguard is a device or mechanism for ensuring safety. An example of a Safeguard is:
A)Everything listed here
B) High steam pressure fuel cut-off
C) Low gas pressure fuel cut-off switch
D) Low water level fuel cut-off
E) Low air pressure fuel cut-off

A

A) Everything listed here

21
Q

Operating controls for hot water boilers are not operated by:
A) Liquid expansion
B) Water temperature changes
C) Sensing bulb and capillary tube
D) Steam pressure
E) Bellows controls

A

D) Steam pressure

22
Q

Common control switches found on low-pressure heating boilers may include:
A) Auto-manual selector switch
B) Low and high fire switches
C) All the switches described here
D) Flame control switch
E) Damper positioning switch

A

C) All the switches described here

23
Q

The On-Off pressure controller contains two adjustable variables, one is the pressure adjustment and the other is the:
A) Cut-in Lever
B) Operating lever
C) Levelling indicator
D) Pressure bellows
E) Differential adjustment

A

E)Differential adjustment

24
Q

The modulating fire control system uses _____ to control the combustion process.
A) Variable fuel/air flow
B) Fuel on-off control
C) Air on-off control
D) Fixed fuel flow and variable air flow
E) Fixed air flow and variable fuel flow

A

A) Variable fuel/air flow

25
Q

Controls found on heating boilers include:
1. Operating controls
2. Pressure relief controls
3. High limit cut-off controls
4. Condensate level controls
5. Low limit cut-off switches

A) 1,2,3
B)2,3,4
C) 1,3,5
D) 3,4,5

A

C) 1,3,5

26
Q

The high limit control of a steam heating boiler should operate at the:
A) Maximum allowable working pressure
B) Blowdown pressure of the safety valve
C) Between the set pressures of the operating control and safety valve
D) Set pressure of the safety valve
E) Cut-out pressure of the operating control

A

C) Between the set pressures of the operating control and safety valve

27
Q

Damper position switches are found on boilers with the following burner control systems:
1. On-off control
2. High-low control
3. Modulating control
4. High-limit control

A) 3,4
B) 1,3
C) 1,2
D)2,3
E)4,5

A

D) 2,3

28
Q

The hot water heating boiler burner control uses the ______ as the sensed variable
A) Boiler steam temperature
B) Drum water level
C) Boiler water pressure
D) Boiler water temperature
E) Feedwater pressure

A

D)Boiler water temperature

29
Q

The High-Low fire control method requires two pressure controllers, one is called the high-low fire control and the other is called the:
A) High limit control
B) On-off fire control
C) Operating limit fire control
D) Operating limit pressure control
E) Modulating fire control

A

D) Operating limit pressure control

30
Q

An automatic/manual selector switch is provided on a boiler with the following burner control system
A) High-Low fire control
B) On-Off fire control
C) Operating limit fire control
D) Modulating fire control
E) High limit fire control

A

D) Modulating fire control

31
Q

If the pressure of the gas supplied to the burner drops below a minimum value the ____ switch will de-energize the fuel valve.
A) Low gas pressure
B) High gas pressure
C) Low water level
D) High limit
E) Low air pressure

A

A) Low gas pressure

32
Q

The low air pressure cut-off switch can be tested by:
A) Quickly closing the main burner shut-off valve
B) Closing the main gas valve quickly
C) Slowly raising the boiler pressure above the operating setpoint
D) Slowly closing the main gas valve
E) Slowly covering the air supply to the fan

A

E) Slowly covering the air supply to the fan