Book 1 Chapter 4: Electric Boilers Flashcards
An immersion-type electric boiler has:
A) electrodes
B) no steam space
C) elements
D) tube bundles
C) elements
The load on an electrode-type electric boiler is maintained by the:
A) amount of steam space in the boiler
B) amount of electrode covered by water
C) outdoor temperature
D) amount of current flowing through the elements
B) amount of electrode covered by water
Output of an immersion electric boiler is regulated by altering the:
A) water level relative to the electrodes
B) water level relative to the elements
C) amount of current flowing through the water
D) amount of current flowing through the elements
D) amount of current flowing through the elements
A main disadvantage of an electric boiler is the:
A) high cost of manufacturing
B) high cost of the electricity
C) inefficiency of the energy transfer
D) space requirement per unit output
B) high cost of electricity
Electric boilers:
A) require tall stacks for pollution dispersement
B) tend not to be very compact
C) require sootblowers when the fuel is coal
D) have energy conversion effiencies close to 100%
D) have energy conversion effiencies close to close 100%
A salinity feeder is an important component of a/an ________ boiler:
A) verticle tubeless
B) electrode-type electric
C) vertical firetube
D) immersion electric
B) electrode-type electric
An immersion type of electric boiler:
A) Does everything shown here
B) Depends on water level to regulate steam production
C) Generates heat utilizing a bundle of heating elements
D) Uses pressure to directly regulate energy consumption
E) Passes current through the water
C) Generates heat utilizing a bundle of heating elements
In an electrode type of electric boiler:
A) As generating zone water level decreases, current increases
B) More steam is generated when the generating zone level drops
C) Current decreases as pressure drops
D) Current increases as the generating zone level drops
E) Electrical current decreases as pressure goes up
E) Electrical current decreases as pressure goes up
Electrode type boilers:
A) Require complex control systems
B) Require external resistance for control
C) Require electrodes to be totally immersed in water
D) Self regulate steam pressure
E) Require microprocessor control
D) Self regulate steam pressure
Water level in the generating zone of an electrode type boiler:
A) Is maintained by means of a feedwater regulator
B) Has no effect on pressure
C) Is governed by feedwater flow
D) Is governed by load fluctuations
E) Is constant
D) Is governed by load fluctuations
A rise of steam pressure in the generating zone of an electrode boiler leads to:
A) A drop in water level in the generating zone
B) More steam output
C) A rise in water level
D) More current demand
E) A requirement of more feedwater
A) A drop in water level in the generating zone
Immersion boiler tube bundles:
A) Act to conduct current through the water
B) Cannot be used to regulate steaming capacity
C) Operate at only one voltage
D) Have very low electrical resistance
E) Can be removed from the unit for maintenance purposes
E) Can be removed from the unit for maintenance purposes
Electric boilers:
A) Tend not to be very compact
B) Require sootblowers when fuel is coal
C) Have energy conversion efficiencies close to 100%
D) Require tall stacks for pollution dispersment
E) Are not as safe as other boilers
C) Have energy conversion efficiencies close to 100%
In an electrode type electric boiler the generating zone:
A) Is less efficient than an immersion type
B) Generates more steam as water levels falls
C) Is less efficient when water level rises
D) Uses more current when water level rises
E) Generates more steam as water level rises
E) Generates more steam as water level rises
Due to the effect of high temperature on the electrodes, Electric boilers are:
A) Operated at lower pressures below 2100kPa
B) Able to withstand any pressure
C) Operated at pressure up to 2100 psi
D) Limited to 1100kPa
E) Required to be used only for large scale industrial processes
A) Operated at lower pressure below 2100kPa