Book 1 Chapter 5: Basic Fittings For Steam Boilers Flashcards
The type of gauge that is commonly used to indicate steam pressure inside a boiler is the _______ gauge:
A) gauge glass
B) bourdon tube
C) safety
D) directly attached
B) bourdon tube
To protect the pressure gauge from the high temperature of the steam a _______ is installed between the steam and the gauge
A) check valve
B) stop valve
C) vacuum tube
D) pipe syphon
D) pipe syphon
You would test a boiler pressure gauge while in service by using a ________.
A) dead weight tester
B) hydraulic tester
C) master test gauge
D) pop test
C) master test gauge
The ________ valve protects the boiler when the pressure approaches its maximum allowable working pressure
A) vent
B) safety
C) check
D) blowoff
B) safety
The lowest visible part of the water gauge glass will be above the ________ recommended by the manufacturer
A) lowest permissible manufacturer
B) fire line
C) top of the firetubes
D) middle try cock
A) lowest permissible manufacturer
An advantage of using a water column is that it:
A) allows air to escape when filling the boiler
B) will indicate the boiler pressure
C) makes the water level easier to read
D) prevents water and steam from escaping if the gauge glass breaks
C) makes the water level easier to read
The blowoff connection on a boiler is made:
A) at the lowest permissible water lead
B) just below the safety valve connection
C) at the lowest point of the boiler
D) just below the feedwater inlet
C) at the lowest point of the boiler
The purpose of the pipe siphon installed between the boiler and the pressure gauge is to prevent:
A) Air from entering the boiler
B) Air from entering the gauge
C) Host steam from entering the boiler
D) Water from entering the gauge
E) Hot steam from entering the gauge
E) Hot steam from entering the gauge
LP steam boilers must be equipped with a marker indicating the:
A) Fireline
B) Maximum water level line
C) Lowest visible water line
D) Low water fuel cut-off line
E) Lowest permissible water line
E) Lowest permissible water line
If a gauge glass breaks, the operator shall immediately:
A) Add more water to the boiler
B) Lift the safety valve
C) Shut the boiler down
D) Shut the fuel valve
E) Shut off the steam valve and water valve on the gauge
E) Shut off the steam valve and water valve on the gauge
The try lever test should be done and recorded in the log book:
A) Annually
B) Weekly
C) At the beginning of every shift
D) Monthly
E) Daily
D) Monthly
A disadvantage of a gauge glass safety-shutoff valve is it:
A) Requires more maintenance
B) Makes gauge glass replacement more difficult
C) Cannot prevent water loss
D) Cannot be blown down
E) Cannot withstand high pressure
A) Requires more maintenance
What is the first step in replacing a broken gauge glass tube after securing proper PPE?
A) Isolate the boiler
B) Lower boiler level below the glass
C) Close the gauge glass isolators and open drain
D) Shut off the feedwater
E) Open the water column drain valve
C) Close the gauge glass isolators and open drain
The “try lever test” is performed by:
A) Bypassing the high pressure limit control
B) All of the above
C) Manually lifting the safety valve off of its seat
D) Raising boiler pressure to MAWP
E) Shutting the boiler stop valve
C) Manually lifting the safety valve off of its seat
Boiler outlet valves are usually:
A) Globe valves because of their throttling capability
B) Globe valves because of their low flow resistance
C) Installed in tandem
D) Gate valves because of the ability to control flow
E) Gate valves because of their low resistance to flow
E) Gate valves because of their low resistance to flow