Book 2 Chapter 20: Refrigeration Accessories Flashcards
At least __________ pressure gauges are normally used on a refrigeration system.
A) 2
B) 3
C) 4
D) 5
A) 2
Which of the following statements are correct pertaining to the location of the sight glass?
A) The sight glass will be installed at the receiver or condenser-receiver outlet if it is used to indicate whether the system is fully charged
B) The glass is installed before the expansion valve if is used to indicate if the refrigerant contains any flash vapour
C) If the glass is combined with a moisture indicator, and the liquid line from the receiver has a drier, then the glass should be installed between the drier and the expansion valve
D) All are correct
D) All are correct
The type of piping and tubing material used in a refrigeration system depends upon the:
A) Size of the piping and tubing required
B) Refrigerant used
C) Application
D) All of the above
D) All of the above
What size of pipe schedule should be used when the diameter of steel piping is 25mm or less?
A) 40
B) 80
C) 120
D) 160
B) 80
The diffuser on the emergency release line is placed not less than _________ away from any windows or other openings.
A) 2.4m (7.87ft)
B) 4.8m (15.75ft)
C) 7.6m (24.93ft)
D) 10m (32.81ft)
C) 7.6m (24.93ft)
A chemical dot placed under the glass lens of a sight glass that is exposed to liquid refrigerant is used to indicate the:
A) Liquid flow
B) System pressure
C) Refrigerant level
D) Presence of moisture
E) Presence of foreign particles
D) Presence of moisture
In order to have even refrigerant flow in a direct expansion type evaporator that has more than one refrigerant circuit, the system requires a/an:
A) Stop valve
B) Distributor
C) Expansion valve
D) Thermal regulator
E) Purge valve
B) Distributor
Which of the following statements about refrigeration pressure gauges is true?
A) Only one pressure gauge is required for each system
B) Dials on refrigeration pressure gauges do not indicate saturation temperature
C) Permanently installed pressure gauges shall be constructed for at least 1.5 times the design pressure
D) They indicate pressures and corresponding temperatures in a system
E) Pressure gauges will not work if the system is equipped with pulsation dampers
D) They indicate pressures and corresponding temperatures in a system
Which of the following pipe joints may be used for pressure exceeding 1750 kPa and 1 1/4 inch or smaller iron and steel piping?
A) Flared
B) Screwed
C) Soldered
D) Welded
E) None of these options
B) Screwed
The accessory that maintains efficient heat transfer by collecting oil that coats the tubes of the condenser is called a/an:
A) Filter
B) Strainer
C) Oil separator
D) Oil scrubber
E) Strainer-drier
C) Oil separator
Which of the following statements about strainers is false?
A) The strainer is installed in the suction line
B) Strainers prevent foreign particles from damaging compressor valves
C) Piping must be disconnected to clean the strainer
D) Strainers typically consist of a fine mesh screen basket
E) Hermetic type compressors are equipped with a built-in suction strainer
C) Piping must be disconnected to clean the strainer
A simple trap located in the suction line before the compressor that collects liquid, where it evaporates and returns to the compressor as a gas, is called a/an:
A) Strainer-drier
B) Accumulator
C) Oil separator
D) Distributor
E) Stop valve
B) Accumulator
A pressure relief device on a refrigeration system shall have sufficient capacity to prevent the pressure in the pressure vessel from rising more than ________ above the setting of the pressure relief device.
A) 20%
B) 15%
C) 10%
D) 25%
E) 50%
C) 10%
Where must refrigeration system Vibration Absorbers be placed to most effectively absorb vibration and noise from the compressor?
A) In piping parallel with the compressor crankshaft
B) To the compressor enclosed housing
C) Attached directly to the side of the compressor
D) Attached to the crankshaft
E) Perpendicular to the compressor crankshaft
A) In piping parallel with the compressor crankshaft
B52-05 code requires an emergency discharge valve in a Glass fronted red box outside the building. Other requirements include:
A) Manually operated valve on a horizontal pipe inside the building
B) Manually operated valve on a horizontal pipe
C) Automatically operated valve on a vertical discharge pipe
D) Remotely operated valve on a horizontal pipe
E) Manually operated valve on a vertical pipe
B) Manually operated valve on a horizontal pipe