The scale on the dial of a pressure gauge shall have a maximum graduation of ________ times the pressure at which the pressure relief valve is set to open.
A) 4.0
B) 3.5
C) 2.5
D) 1.5
B) 3.5
Where should the pressure relief valve be installed in a hot water system?
Anywhere reasonably close to the tank
The wax filled sensor probe in a combination pressure-temperature relief valve will expand and open the valve by means of a piston at approximately:
A) 50C (122F)
B)110C (230F)
C) 99C (210F)
D) 134C (273F)
C) 99C (210F)
The maximum size of the blowoff or drain connection on a hot water heating boiler is:
A) NPS 1/2 (DN15)
B) 25mm OD
C) NPS 3/4 (DN20)
D) 2 inches ID
C) NPS 3/4 (DN20)
The automatic fill valve is a/an ___________ valve, which keeps the system filled with water and maintains a set pressure in the system.
A) pressure reducing
B) air vent
C) back pressure
D) pressure control
A) pressure reducing
The relief valve on hot water boilers with a working pressure of up to 414 kPa(60psi) should open with in a variation of _______below or above the set point.
A) 5%
B) 20kPa (3psi)
C) 10kPa (1.5psi)
D) 14%
E) 30kPa (4.5psi)
B) 20kPa (3psi)
The minimum size of the hot water boiler bottom blow off or drain connection shall be:
A) 15mm (1/2in)
B) 6mm (1/4in)
C) 75mm (3in)
D) 19mm (3/4in)
E) 25mm (1in)
D) 19mm (3/4in)
The highest pressure to which the scale on the pressure gauge of a hot water boiler may be graduated is_____ times the pressure at which the pressure relief valve is set.
A) 3.5
B) 2
C) 1.5
D) 2.5
E) 3
A) 3.5
The wax filled sensor probe in a combination pressure-temperature relief valve will expand and open the valve by means of a piston at approximately:
A) 60C (140F)
B) 110C (230F)
C) 134C (273F)
D) 50C (122F)
E) 99C (210F)
E) 99C (210F)
The purpose of the expansion tank in a hot water heating system is to:
A) Separate the water and steam produced
B) Provide storage space for excess water
C) Provide storage space for excess steam
D) Add make-up water to the system
E) Provide space to store the returning condensate
B) Provide storage space for excess water
The automatic fill valve is a ______ valve which keeps the system filled with water and maintains a set pressure in the system.
A) Back pressure valve
B) Pressure reducing valve
C) Temperature control valve
D) Pressure control valve
E) Air vent valve
B) Pressure reducing valve
The pressure relief valve is typically installed on the boiler or reasonably close to the boiler outlet with:
A) A ball valve for isolation
B) A globe valve for isolation
C) A plug valve for isolation
D) No valve between
E) A gate valve for isolation
D) No valve between
The discharge piping from the relief valve should be piped to a safe point of disposal and can be:
A) Connected to the deaerator
B) Connected to any vent
C) Connected to the condensate tank
D) Terminated above a floor drain
E) Connected to any drain
D) Terminated above a floor drain
The operating handle of the valve to the pressure gage on a hot water boiler must be of the:
A) Hand wheel type
B) Solenoid type
C) Tee or lever handle design
D) Diaphragm type
E) A valve is not permitted in this location
C) Tee or lever handle design
On a hot water boiler, the highest value on the graduated scale of the pressure gauge shall not be less than _____ times the pressure at which the pressure relief valve is set.
A) 1.5
B) 3.5
C) 3
D) 2.5
E) 2
A) 1.5