The _______ operated low water fuel cut-off uses buoyancy to operate the switch.
A) float
B) electrode
C) bi-metal
D) thermal
A) float
The type of low water fuel cut-off that uses the conductivity of the water to operate it is the __________ type.
A) float
B) thermal
C) three wire
D) electrode probe
D) electrode probe
The main cause of heating boiler failure is overheating of the heating surfaces due to:
A) high water level
B) too high a steam pressure
C) low water level
D) operator error
C) low water level
A low water fuel cut-off combination pump will _____ if the water level reaches a low level, but still above the lowest permissible level.
A) shut down the boiler
B) start the feewwater pump
C) close the fuel valve
D) open the safety valve
B) start the feedwater pump
Low water levels can develop in hot water boilers due to human error.
A) true
B) false
A) true
On a steam boiler, test the low water fuel cut-off while the boiler is operating by:
A) increasing the steam pressure
B) blowing down the boiler
C) opening the drain valve on the float chamber
D) doing a “pop” test
C) opening the drain valve on the float chamber
A three wire (double pole) switch on a LWFCO will shut off the fuel and sound an alarm.
A) true
B) false
A) true
At normal boiler steaming rates, a condensate receiver tank should have enough water supply to keep the boiler supplied for ________ minutes.
A) 30
B) 15
C) 45
D) 60
A) 30
A leak in a condensate return pipe can cause:
A) Less fuel to be burned
B) A decrease in system water use
C) Less corrosion in the condensate system
D) A low boiler water condition
E) Less chemicals to be required
D) A low boiler water condition
Equalizing lines on a condensate receiver float chamber:
A) Maintain make-up flow equal to condensate flow
B) Eliminate the need for a make-up level control valve
C) Keep receiver level equal to boiler level
D) Will dampen level fluctuations
E) Maintains equal flow of condensate to multiple boilers
D) Will dampen level fluctuations
A hot water boiler low water fuel-cutoff:
A) Should be located on the expansion tank
B) Cannot be tested during routine boiler operation
C) Should be tested weekly during routine boiler operation
D) Cannot be tested
E) Must have a normally closed switch
B) Cannot be tested during routine boiler operation
The low water fuel cut-off may be tested by:
A) Opening the gauge glass drain
B) Decreasing the firing rate
C) Adjusting the level controller to maximum
D) Closing the feedwater inlet valve and opening the blowdown valves
E) Opening the feedwater inlet valve closing the blowdown valves
D) Closing the feedwater inlet valve and opening the blown down valves
Low hot water heating boiler water level can be caused by:
A) Feedwater flow exceeding steam flow
B) Excessive blowdown (blowoff)
C) Swell in the boiler
D) High boiler conductivity
E) Low phosphate leve
B) Excessive blowdown (blowoff)
When a boiler equipped with a combination feedwater control and low water cutoff device shuts down due to a low water condition:
A) Level must be restored to above the cut-off line before the unit can be restarted
B) A manual reset switch on the boiler control panel must be used
C) A prepurge of the boiler before it is restarted will not be necessary
D) The feedwater flow to the condensate receiver tank will also stop
E) It can be restarted by simply resetting the low water fuel cut-off switch
A) Level must be restored to above the cut-off line before the unit can be restarted
On LP steam heating boilers, the low water fuel cut-off should operate when:
A) There is excessive blowdown or leakage
B) The boiler water level drops below 25mm (1in) in the gauge glass
C) The float chamber drain is opened
D) The boiler feedwater flow is stopped during operation
E) All of the above
E) All of the above