What units must complete reactive testing?

A
  • Individual units > 20 MVA and aggregate units > 75 MVA
  • All units designated Black Start
  • All Synchronous Condensers > 20 MVA
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How often is reactive testing required?

A

Every 5 years.

no more than 66 mo. between tests

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When does an eDART ticket need to be submitted prior to reactive testing?

A

No later than 3 business days prior

Create “MVAR Test” ticket

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Day of test notification requirements

A

Notify PJM RE at least 3 hours before start of test.

Notify PJM transmission & TO 30 min before start.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Units should be tested against their expected capability, for example, __________

A

For new units, vendor D curve

For existing units, previous test results would be an expected minimum.