6.3 Reactive Capability Testing & Net Capability Testing Flashcards
1
Q
What units must complete reactive testing?
A
- Individual units > 20 MVA and aggregate units > 75 MVA
- All units designated Black Start
- All Synchronous Condensers > 20 MVA
2
Q
How often is reactive testing required?
A
Every 5 years.
no more than 66 mo. between tests
3
Q
When does an eDART ticket need to be submitted prior to reactive testing?
A
No later than 3 business days prior
Create “MVAR Test” ticket
4
Q
Day of test notification requirements
A
Notify PJM RE at least 3 hours before start of test.
Notify PJM transmission & TO 30 min before start.
5
Q
Units should be tested against their expected capability, for example, __________
A
For new units, vendor D curve
For existing units, previous test results would be an expected minimum.