Reactor, MFP, and Turbine Trips Flashcards
List the Rx Trips
- SR High Flux
- IR High Flux
- PR High Flux, Low Setpoint
- PR High Flux, High Setpoint
- PR High Rate
- OTΔT
- OPΔT
- PZR High #
- PZR Low #
- PZR Level High
- RCS Loss of Flow
- RCP Busses UV
- RCP Busses UF
- RCP Breaker Position
- SGWL Lo-Lo
- SGWL Lo with Feed Flow < Steam Flow
- SI
- Turbine Trip
List the “At Power” Rx Trips
- PZR Low #
- PZR Level High
- RCS Loss of Flow
- RCP Busses UV
- RCP Busses UF
- RCP Breaker Position
SR High Flux Trip Coincidence, Setpoint, and Interlock
- 1/2 SR NI
- 9 x 10^4 CPS
- P-6
IR High Flux Trip Coincidence, Setpoint, and Interlock
- 1/2 IR NI
- Current equivalent of 22.5% RTP (20)% RTP
- P-10
PR High Flux Trip (Low) Coincidence, Setpoint, and Interlock
- 2/4 PR NI
- 20% RTP
- P-10
PR High Flux Trip (High) Coincidence, Setpoint, and Interlock
- 2/4 PR NI
- 107% RTP
- No Interlock
PR High Positive Rate Trip Coincidence, Setpoint, and Interlock
- 2/4 PR NI
- 4.5% rise in 2 seconds
- No Interlock
OTΔT Trip Coincidence, Setpoint, and Interlock
- 2/4
- Variable Setpoint
- No Interlock
OPΔT Trip Coincidence, Setpoint, and Interlock
- 2/4
- Variable Setpoint
- No Interlock
PZR High # Trip Coincidence, Setpoint, and Interlock
- 2/4 # detectors
- 2385 #
- No Interlock
PZR Low # Trip Coincidence, Setpoint, and Interlock
-2/4 detectors
- 1950#
- P-7 Interlock
RCS Loss of Flow Coincidence, Setpoint, and Interlock
- 2/3 detectors on 1/4 loops (2/3 detectors on 2/4 loops)
- 91% (91%)
- > P-8 (< P-8, but > P-7)
PZR High Water Level Coincidence, Setpoint, and Interlock
- 2/3 detectors
- 92%
- P-7 Interlock
RCP Busses UV Trip Coincidence, Setpoint, and Interlock
- 1/2 on 2/4 busses
- 88 V
- P-7 Interlock
RCP Busses UF Trip Coincidence, Setpoint, and Interlock
- 1/2 on 2/4 busses
- 58.2 Hz
- P-7 Interlock