C-1 Coincidence, Setpoint, and Function

A
  • 1/2 IR NI
  • At approximately 18% U1 (16% U2)
  • Auto and Manual Rod Withdrawal Stop
    (Manually blocked above P-10, auto un-blocked below P-10)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

C-2 Coincidence, Setpoint, and Function

A
  • 1/4 PR NI
  • At 103%
  • Auto and Manual Rod Withdrawal Stop
    (Rod stop bypass on drawer)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

C-3 Coincidence, Setpoint, and Function

A
  • 2/4 OTΔT
  • 3% < Trip Setpoint
  • Auto and Manual Rod Withdrawal Stop and Initiates Turbine Runback
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

C-4 Coincidence, Setpoint, and Function

A
  • 2/4 OPΔT
  • 3% < Trip Setpoint
  • Auto and Manual Rod Withdrawal Stop and Initiates Turbine Runback
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

C-5 Coincidence, Setpoint, and Function

A
  • 1/1 Impulse # (MPC-253)
  • < 15%
  • Auto Rod Withdrawal Stop
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

C-7A Coincidence, Setpoint, and Function

A
  • MPC-254
  • 10% load rejection
  • Arms group 1 & 2 steam dump valves for load rejection
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

C-7B Coincidence, Setpoint, and Function

A
  • MPC-254
  • 30% load rejection
  • Arms group 3 steam dump valves for load rejection
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

C-8 Coincidence, Setpoint, and Function

A
  • 4/4 turbine stop valves OR 2/3 oil pressure switches
  • Stop valves closed (<1% open) OR oil pressure < 800#
  • Arms groups 1 & 2 steam dumps and disarms group 3, automatically selects the turbine trip controller for steam dumps.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

C-9 Coincidence, Setpoint, and Function

A
  • 1 Circ Pump Breaker closed, AND CRID 2 energized, AND 3/3 Condenser Vacuum ≥ 20.6” Hg
  • Energized: Unblocks Steam Dump Operation
  • De-energized: Blocks Steam Dumps
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

C-11 Coincidence, Setpoint, and Function

A
  • No coincidence
  • Bank D demand at 229 steps
  • Auto rod withdrawal stop
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

C-20 Coincidence, Setpoint, and Function

A
  • 2/2 Turbine Impulse #
  • # > 40%
  • Enables:
    1) AMSAC
    2) Turbine Trip
    3) MDAFP Start
    4) TDAFP Start
How well did you know this?
1
Not at all
2
3
4
5
Perfectly