ESF Actuations Flashcards
1
Q
What will cause an SI?
A
- Manual
- High Containment Pressure (2/3 @ 1# rising)
- Low PZR # (2/3 @ 1775# lowering)
- Differential Pressure Between Steam Lines (2/3 detectors and 1S/G < 2 others, 100#)
- Low SG # (2 S/G’s <500#)
2
Q
What will cause Containment Spray?
A
- Manual
- Hi-Hi Containment # (2/4 @ 2/8# rising)
3
Q
What will cause Containment Isolation Phase “A”?
A
- Manual
- SI Actuation
4
Q
What will cause Containment Isolation Phase “B”?
A
- Manual
- CTS Actuation
5
Q
What will cause a Steam Line Isolation?
A
- Manual
- Hi-Hi Containment # (2/4 @ 2.8#)
- High Steam Flow (1/2 on 2 S/G’s, 1.42E6(1.6E6)lbm/hr) with P-12 (2/4 loop Tavg < or
equal to 541F) - Low SG # (On 2 S/G’s <500#)
6
Q
What will cause a Turbine Trip AND FWI?
A
- Hi-Hi SGWL (2/3 on 1 S/G @ 67%)
- SI
- Rx Trip with Low Tave
7
Q
What will cause MDAFP’s to start?
A
- Lo-Lo SGWL (2/3 NR on 1S/G @ 5%(22%))
- 4kV Bus Loss of Voltage (2/3 on T-A or T-D busses, <94V(<93V))
- 4kV Bus Loss of Voltage (2/3 on BOTH T busses in same train, <94V(93V))
- SI
- Loss of both MFP’s (2/2 stop valves closed) (Only when switch in AUTO)
- AMSAC (3/4 FW flow <25%)
8
Q
What will cause TDAFP to start?
A
- Lo-Lo SGWL (2/3 on 2 S/G’s @ 5%(22%))
- RCP Bus UV (1/2 on 2/4 busses @ 88V lowering)