ESF Actuations Flashcards

1
Q

What will cause an SI?

A
  • Manual
  • High Containment Pressure (2/3 @ 1# rising)
  • Low PZR # (2/3 @ 1775# lowering)
  • Differential Pressure Between Steam Lines (2/3 detectors and 1S/G < 2 others, 100#)
  • Low SG # (2 S/G’s <500#)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will cause Containment Spray?

A
  • Manual
  • Hi-Hi Containment # (2/4 @ 2/8# rising)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will cause Containment Isolation Phase “A”?

A
  • Manual
  • SI Actuation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What will cause Containment Isolation Phase “B”?

A
  • Manual
  • CTS Actuation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What will cause a Steam Line Isolation?

A
  • Manual
  • Hi-Hi Containment # (2/4 @ 2.8#)
  • High Steam Flow (1/2 on 2 S/G’s, 1.42E6(1.6E6)lbm/hr) with P-12 (2/4 loop Tavg < or
    equal to 541F)
  • Low SG # (On 2 S/G’s <500#)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What will cause a Turbine Trip AND FWI?

A
  • Hi-Hi SGWL (2/3 on 1 S/G @ 67%)
  • SI
  • Rx Trip with Low Tave
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What will cause MDAFP’s to start?

A
  • Lo-Lo SGWL (2/3 NR on 1S/G @ 5%(22%))
  • 4kV Bus Loss of Voltage (2/3 on T-A or T-D busses, <94V(<93V))
  • 4kV Bus Loss of Voltage (2/3 on BOTH T busses in same train, <94V(93V))
  • SI
  • Loss of both MFP’s (2/2 stop valves closed) (Only when switch in AUTO)
  • AMSAC (3/4 FW flow <25%)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What will cause TDAFP to start?

A
  • Lo-Lo SGWL (2/3 on 2 S/G’s @ 5%(22%))
  • RCP Bus UV (1/2 on 2/4 busses @ 88V lowering)
  • AMSAC (3/4 FW flows <25%)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly