PZR Flashcards
What is PZR Control Level Program
0-15% PWR - 33% lvl
15-100% PWR - linear to 52.5%
PZR Heater Interlocks
PZR Heaters Off
<25% Level or
>2285 psia
SIAS (class only)
(Note: Reset @27%)
What is the PZR heater Setpoint Override?
Initiated by taking the heater bank control switch (HS-100-4, 5, 6, 7, 8, 9) firstly to OFF then to ON.
- A white OVERRIDE light illuminates to indicate this mode.
- After a 10 second time delay, the override can be canceled by taking the control switch to OFF.
- 10 seconds must then elapse before the override can be re-initiated.
What is the purpose of the SIAS Override?
Class 1E powered backup heater banks trip on SIAS
SIAS Override allows these heater banks to be reenergized with a SIAS present.
- Initiated in the same manner as the Normal Setpoint Override.
- Once initiated, the heater banks can be de-energized and re-energized as desired.
- This override permissive remains in effect until the SIAS signal is reset.
CHG pump Level Deviation Program
(+15% and increasing) Normally Running Pump - Stops
(+14% and decreasing) Normally Running Pump - Restarts
(-14% and increasing) Standby Pump - Stops
(-23% and decreasing) Standby Pump - Starts
PZR Heater Level Deviation Program
(+3% and increasing) Hi Level Dev. Backup Heaters - ON (Anticipated in-surge)
(+2.5% and decreasing) Hi Level Dev. Resets Back up Heaters - OFF
Unit is operating at 50% power.
Letdown begins reducing rapidly.
The operator selected the alternate PZR level channel but the trend continues.
Which one of the following could be the cause?
A. Thot input to RRS has failed high.
B. Tc input to RRS has failed low.
C. Pressurizer pressure instrument has failed high.
D. Pressurizer pressure instrument has failed low.
A. Thot input to RRS has failed high.
Unit is operating at rated power.
The Pressurizer Master Controller is in REMOTE and MANUAL.
Pressurizer level is being maintained at approximately 52%.
The Pressurizer Level Control selector switch is in the ‘X’ position.
RRS is aligned to monitor the average Tavg.
RCN-TT-111X (Thot) input into the RRS fails low.
Which one of the following (if any) describes an expected response?
A. This failure will have no impact.
B. All backup heaters energize.
C. The standby charging pump starts.
D. The letdown control valve throttles closed.
B. All backup heaters energize.
(Note: The REMOTE portion of this question is useless. It is in MANUAL Control).
The unit is operating at 100% power.
The normally running Charging Pump stops.
Letdown flow increases to maximum then isolates.
Which one of the following instrument failures (if selected) could be the cause of these conditions?
A. Pressurizer level controller loses power.
B. Tc input to reactor regulating system fails low.
C. Pressurizer level transmitter output fails low.
D. Tc input to reactor regulating system fails high.
B. Tc input to reactor regulating system fails low.
Unit is at 35% power.
Pressurizer Level Control System Master Controller (RCN-LIC-110) Remote Auto.
‘Pressurizer Trouble’ Alarm.
Letdown flow starts to lower.
RCN-LIC-110 shows PZR level set point at 53%.
All other system responses are normal.
Which of the following is the probable cause of the failure?
A. NNN-D11 has lost power.
B. T-Cold input to RRS has failed low.
C. T-Cold input to RRS has failed High.
D. Letdown control valve is failing closed due to loss of power.
C. T-Cold input to RRS has Failed High.
Note: Program level at 35% power is 37.6% power. Full power level is 52.5%.
Unit is operating at rated power.
Pressurizer level set point controller (RCN-LIC-110) is in LOCAL-AUTO set at 52%.
Pressurizer level control selector channel X/Y switch is selected to Channel Y.
Pressurizer heater control trip channel X/Y switch in BOTH.
LT-110Y Fails low.
Assuming NO operator action, you should expect CHANNEL X indicated level to…
A. Increase and pressurizer heaters to energize.
B. Decrease and pressurizer heaters to energize.
C. Decrease and pressurizer heaters to de-energize.
D. Increase and pressurizer heaters to de-energize.
D. Increase and pressurizer heaters to de-energize.
(Note: Selector in Local-Auto means that level is controlled per the black set point arrow.
The plant is at 100% power.
PZR level control selected to LT-110X.
A loss of NNN-D11 occurs.
Which of the follow describes the effect on the Pressurizer Level Control System?
A. PZR level control RCN-LT110X and RCN-LT110Y are lost.
B. The PZR level controller RCN-LIC-110 fails to zero.
C. The standby charging pump will start.
D. PZR level control channel RCN-LT-110X loses power.
B. The PZR level controller RCN-LIC-110 fails to zero.
Which one of the following describes the function(s) of high pressure interlock in the PPCS?
A. Causes a signal to be sent to the PPS to trip the reactor if pressure exceeds 2383 psia.
B. Energized all the backup heaters at 2285 psia but has no impact on proportional heaters.
C. De-energizes all the backup heaters at 2285 psia. Has no impact of proportional heater operations.
D. De-energizes all pressurizer heaters at 2285 psia.
D. De-energizes all pressurizer heaters at 2285 psia.
A SIAS has occurred. Which statement below best describes the effect of the SIAS on the pressurizer heaters?
A. The proportional heaters are not affected.
B. All backup heaters trip and they cannot be re-energized unless the SIAS override is initiated.
C. The class backup heaters trip and they cannot be re-energized unless the SIAS is reset.
D. The non-class backup heaters trip and cannot be re-energized unless taken to set point override.
A. The proportional heaters are not affected.
Unit is operating at 100% full power.
Pressurizer Pressure Control System in AUTO with the set-point at 2250 psia.
Pressurizer pressure is 2270 psia and rising.
Which of the following describes the next automatic action as pressurizer pressure continues to rise?
A. Reactor trip on High Pressurizer Pressure.
B. Reactor Trip on Core Protection Calculators auxiliary trip.
C. Pressurizer backup heaters de-energize.
D. Pressurizer spray valves will modulate open.
D. Pressurizer spray valves will modulate open.
Note:
- Spray valves begin to open at 25 psi above set point. Spray valves are full open at 50 psi above setpoint.
- Reactor Trip on High Pressurizer Pressure (2383 psia)
- Pressurizer backup heaters de-energize (2285 psia)