DFWCS (Digital Feed Water Contrl Signal) Flashcards
Which one of the following describes the level transmitter signal(s) used for SG level control on SG 1 DFWCS when it is in a normal configuration?
A. The higher output of LT-1111 and LT-1112.
B. The output of LT-1111 only.
C. The lower output of LT-1111 and LT-1112.
D. The average output of LT-1111 and LT-1112.
A. The higher output of LT-1111 and LT-1112.
Unit is at 16% power.
All control systems are operating normally, in automatic.
MFP ‘A’ is operating at 4150 rpm with 0 bias.
An Operator adds MINUS 100 rpm bias to the ‘A’ main feed pump controller.
MFP ‘A’ is now operating at…
A. 4050 rpm, and will increase speed based on master controller output.
B. 4050 rpm, and will be unaffected by small master controller output changes.
C. 4150 rpm, and will slow to 4050 rpm if the master controller goes into single element control.
D. 4150 rpm, and will be unaffected if the master controller goes to single element control.
D. 4150 rpm, and will be unaffected if the master controller goes to single element control.
Assume that all digital feedwater control system control input transmitters are in service and selected to AVERAGE.
The plant is at 15.5% power.
Power is slowly increasing.
Steam Generator #1 downcomer valve position 80% and is opening slowly.
Steam Generator #2 downcomer valve position is 70% and is opening slowly.
Concerning the digital feedwater control system, which (if any) of the following automatic actions will occur?
A. No DFWCS automatic action will occur until 16.5% power is reached.
B. No DFWCS automatic action will occur until both SG downcomer valves are 80% open.
C. Only SG #1 will go through swap over.
D. Both SG #1 and SG #2 will go through swap over.
D. Both SG #1 and SG #2 will go through swap over.
At rated power.
FWCS #1 Master in manual with 50% output.
FWCS #2 Master in automatic with 50% output.
A Reactor Trip occurs.
Which one of the following is true?
A. FWCS #2 will enter RTO, FWCS #1 will not.
B. Both FWCS will enter RTO and feed based on Tavg ONLY.
C. Both FWCS will enter RTO and remain in RTO if SG levels are <51.9% NR.
D. Bot FWCS will enter RTO, but FWCS #1 will continue to feed past 51.9% NR level.
C. Both FWCS will enter RTO and remain in RTO if SG levels are <51.9% NR.
Unit 1 is operating at rated power.
Both Feed water control systems are in auto.
SGN-LT-1111, SG-1 Level fails High
Based on these conditions, the operator can expect:
A. Feed pump speed to lower.
B. DFWCS (both) enter high level override.
C. SG-1 downcomer and economizer control valves to throttle closed.
D. No effect on DFWCS, alarm only
D. No effect on DFWCS, alarm only
Which of the following inputs to the Digital Feedwater Control System is used for indication only?
A. Downcomer flow transmitters
B. Tavg
C. Turbine Load Index
D. Steam Bypass Master Controller Output
A. Downcomer flow transmitters
Unit 1 is operating at rated power.
DFWCS is in normal line up (No transmitters in maintenance).
RRS has Tavg selected to ‘Average’.
If Tavg fails HIGH during a reactor trip, both DFWCS would…
A. Feed at the maximum rate as permitted by RTO.
B. Be prevented from entering RTO.
C. Prevent feeding of the Steam Generators.
D. Feed at the minimum rate as permitted by RTO.
A. Feed at the maximum rate as permitted by RTO.
Unit 1 is operating at rated power.
DFWCS is in a normal line up.
A feedwater temperature transmitter fails low.
With no operator action, which of the following represents the response of DFWCS?
A. DFWCS shifts to 1E control.
B. Adaptive Tuning (ATUN) Lockout and the temperature transmitter will shift to maintenance mode.
C. DFWCS uses a canned value of 425 degrees for feedwater temperature.
D. DFWCS feeds to the High Level Override setpoint.
C. DFWCS uses a canned value of 425 degrees for feedwater temperature.
How will a momentary loss (10 seconds) of NNN-D11 affect DFWCS at 100% power?
A. DFWCS will be de-energized and return in Manual on the Master Controller.
B. DFWCS will be de-energized and return in single element control.
C. DFWCS will be unaffected; power will transfer to NNN-D12 and remain there until an operator shifts power supplies back to NNN-D11
D. DFWCS will be unaffected; power will transfer to NNN-D12 and then automatically shift back to NNN-D11
D. DFWCS will be unaffected; power will transfer to NNN-D12 and then automatically shift back to NNN-D11.
Rx power is 100%.
All the control input transmitters to the Digital Feedwater Control system are in service and selected to AVERAGE.
If a SG feed flow transmitter fails low which of the following describes the automatic action that would take place in the DFWCS if a 6% deviation between the feed flow transmitters developed?
The affected master controller would:
A. Stay in automatic but in single-element control.
B. Shift to manual with the output signal that was present at the 4% deviation point.
C. Stay in automatic, 3-element control, using the average feedwater flow transmitter signal.
D. Stay in automatic, 3-element control, using the highest feedwater flow transmitter signal only.
C. Stay in automatic, 3-element control, using the average feedwater flow transmitters signal.
(Note: 8% is the deviation to go to single-element)
Unit 1 is at 100% power.
All control input transmitters to the Digital Feedwater Control system (DFWCS) are in service and functioning normally.
A #1 SG level transmitter fails low.
SG #1 DFWCS Master Controller will ____.
A. Remain in automatic 3-element control using the higher indicating level transmitter.
B. Shift to manual single element control.
C. Remain in automatic 3-element control, using the lower indicating level transmitter.
D. Shift to single element automatic control, using the higher indicating level transmitter.
A. Remain in automatic 3-element control using the higher indicating level transmitter.
The plant is at 100% power.
DFWCS is selected to Excore Nuclear Instrumentation Control Channel 1.
The Excore Nuclear Control Channel 1 fails low.
Which ONE of the following describes appropriate operator actions as a result of this failure?
A. No operator action is necessary, ATUN lockout prevents DFWCS response.
B. Take manual control of S/G 1 economizer, downcomer and associated FWPT and restore S/G 1 level; All S/G 2 components are left in automatic.
C. Take the manual control of the S/G 1 and S/G 2 Economizer, Downcomer and FWPT speed and restore S/G levels.
D. Trip the Reactor
D. Trip the reactor
Note: DFWCS is selected to Control Channel 1, answer as assuming its the only operable channel
Unit 1 is operating at rated power.
FWCS #1 Master in manual.
FWCS #2 Master in automatic.
A Reactor Trip occurs.
With no post trip operator action both SG levels are now 55% Narrow Range.
Which of the following is true of the Master Controllers?
A. FWCS #1 is in Auto in 1E control, FWCS #2 is in Auto in 1E control.
B. FWCS #1 is in Auto in 1E control, FWCS #2 is in manual.
C. Both Master Controllers are in RTO tracking.
D. FWCS #1 is in Auto in 1E control, FWCS #2 is RTO tracking.
A. FWCS #1 is in Auto in 1E control, FWCS #2 is in Auto in 1E control.
Unit 1 tripped from 100% power due to a trip of Reactor Coolant Pump 1B and has the following conditions:
DFWCS is in a normal line up (no transmitters in maintenance)
The Reactor Regulating System (RRS) T-avg has failed high.
SG 1 level is recovering and currently 54% NR.
SG 2 level is recovering and currently 45% NR.
Which one of the following describes the status of the Digital Feedwater Control System (DFWCS)?
A. SG 1 and SG 2 are each feeding in single element control.
B. SG 1 and SG 2 are each feeding at the maximum rate as allowed by Reactor Trip Override (RTO)
C. SG 1 is feeding in single element control, SG 2 is feeding at the minimum rate as allowed by Reactor Trip Override (RTO).
D. SG 1 is feeding in single element control, SG 2 is feeding at the maximum rate as allowed by Reactor Trip Override (RTO).
D. SG 1 is feeding in single element control, SG 2 is feeding at the maximum rate as allowed by Reactor Trip Override (RTO).
Assume that all Digital Feedwater Control System (DFWCS) input transmitters are in service and selected to AVERAGE.
An increase to 20% power is in progress.
The plant is currently at 14.5% power by control channel indication.
SG #1 downcomer valve position is 80% and is opening slowly.
SG #2 downcomer valve position is 70% and is opening slowly.
Under these conditions which one of the following is the expected response of the DFWCS system?
A. Only SG 1 should now go through swapover.
B. Both SGs 1 and 2 should n ow go through swapover.
C. Neither SG will go through swapover until >15% power is reached.
D. Neither SG will go through swapover until both SG downcomer valves are >80% open.
C. Neither SG will go through swapover until >15% power is reached.