Which of the following describes the effects of a loss of service air to an Automatic Pre-action Sprinkler System?

A. The deluge valve automatically opens, pressurizing the pipe in that area with water.
B. The individual head will initiate flow to the affected area.
C. The associated deluge valve will open allowing full flow from all spray nozzles.
D. An alarm is received in the control room with no actuation

A

D. An alarm is received in the control room with no actuation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If the Fire Protection Water header pressure drops to 89 psig which of the following describes how many fire pumps are running?

A. Jockey Pump ONLY
B. Jockey Pump, Motor Driven Fire Pump ONLY
C. Jockey Pump, Motor Driven Fire Pump, and one Diesel Driven Fire Pump ONLY
D. Jockey Pump, Motor Driven Fire Pump, and both Diesel Driven Fire Pumps

A

C. Jockey Pump, Motor Driven Fire Pump, and one Diesel Driven Fire Pump ONLY

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Which of the following areas is equipped with an AUTOMATIC carbon dioxide fire suppression system?

A. 13.8 KV Switchgear Room
B. Battery Room for E & F
C. Battery Room ‘D’
D. Remote Shutdown Panel

A

C. Battery Room ‘D’