What is C-1
IR Rod Stop 1/2 IRNI > 18% (16%)
What is C-2
PR Rod Stop 1/4 PRNI >103%
What is C-3
OT Delta T Rod Stop 2/4 PRNI 3% < trip Setpoint
What is C-4
OP delta T Rod Stop 2/4 PRNI 3% < trip setpoint
What is C-5
Turbine Power Interlock MPC-253 < 15%
What is C-7A?
Load rejection bistable. 10% step change or sustained ramp decrease of a given magnitude for a long enough time period
What is C-7B?
Load rejection bistable 30% step change. From turbine impulse pressure MPC-254. Arms steam dump valves for load rejection operation
What is C-11
Control Bank D Rod Stop CBD @ 229 steps (cycle dependent)
What is C-20?
2/2 Turbine impulse pressures (MPC-253 and 254) greater than 40% equivalent power “enables” AMSAC
What does C-1, IR Rod Stop do and when can it be blocked?
Stops Auto and Manual Rod Withdrawl Blocked when IR range High Flux Trip is blocked (P-10) Auto unblocked
What does C-2, PR Rod Stop do and when can it be blocked?
Stops outward rod motion in Auto and Manual Blocked when Rod Stop Bypass selected to alarming channel
What does C-3, OT delta T Rod Stop do and when can it be blocked?
Stops outward rod motion in Auto and Manual Cannot be blocked
What does C-4, OP delta T Rod Stop do and when can it be blocked?
Stops outward rod motion in Auto and Manual Cannot be blocked
What does C-5, Turbine Power Interlock do and when can it be blocked?
Stops outward rod motion in AUTO only Cannot be blocked
What does C-11, Control Bank D Rod Stop do and when can it be blocked?
Stops outward motion in AUTO only Cannot be blocked
Which permissives are there really no status lights for?
P-4 and P-14
What condition will make the P-4 Status Light “ON”?
Both Rx Trip Breaker A and Bypass Breaker A open OR Both Rx Trip Breaker B and Bypass Breaker B open
What is the function of the P-4 Status Light being “on”?
Combines w Low Tavg to give FWI
Seals in FWI from SI or Hi-Hi SG Level
Permits manual block of all automatic SI signals
What condition will make the P4 Status Light OFF?
Either the Rx Trip or Bypass breaker is racked in and closed
What is the function of the P-4 Status Light being “off”?
Prevents or defeats manual block of SI
What condition will make the P-6 Status light ON?
Any IR NI ≥ 10-10 amps and rising
What is the function of the P-6 Status light being On?
Permits manual block of the SR High Flux Trip
What condition will make the P-6 Status light OFF
Both IR NI channels < 6 x 10-11 amps and lowering
What is the function of the P-6 status light being Off?
Prevents or defeats the manual block of the SR High Flux Trip
What condition will make the P-7 Status light ON?
3/4 PRs < 10% AND 2/2 Turbine 1st Stage pressures <10% equivalent power
What is the function of the P-7 Status light being On?
Permits automatic block of Rx trips due to the “at-power” trips
What condition will make the P-7 Status light OFF?
2/4 PRs > 10% OR 1/2 Turbine 1st stage pressures >10% equivalent power
What is the function of the P-7 status light being Off?
Prevents or defeats the automatic block of Rx trips due to the “at-power” trips w exception of turbine trip
What can happen that meets P-7?
Reset of P-10 and actuation of P-13
What condition will make the P-8 Status Light ON?
3/4 PRs less than or equal to 29%
What is the function of the P-8 Status light being ON?
Permits the automatic block of Rx trips due to single loop low flow trips and turbine trip
What condition will make the P-8 Status Light OFF?
2/4 PRs > 29%
What is the function of the P-8 Status light being OFF?
Prevents or defeats the automatic block of a Rx trip due to a single loop low flow trip and turbine trip
What condition will make the P-10 Status light on?
2/4 PRs greater than or equal to 10%
What is the function of the P-10 Status light being on?
Permits the manual block of: 1. PR High Flux Trip, Low Setpoint 2. IR Trip 3. IR Rod Stop Also: 4. Resets P-7 5. Backup deenergization of SR
What condition will make the P-10 Status light OFF?
3/4 PRs < 10%
What is the function of the P-10 Status light being OFF?
Prevents or defeats the manual block of: 1. PR High Flux Trip, Low Setpoit 2. IR Trip 3. IR Rod Stop Also: 4. Inputs into P-7
What does P-10 do?
De-Energizes Source Ranges
What condition will make the P-11 Status light on?
2/3 PRZ pressure < 1910 #
What is the function of the P-11 Status light being on?
Permits manual block of SI actuation on low pressurizer pressure
What condition will make the P-11 Status light off?
2/3 PRZ pressure greater than or equal to 1910 #
What is the function of the P-11 Status light being off?
Prevents or defeats manual block of SI actuation on low pressurizer pressure
What condition will make the P-12 Status light on?
2/4 Loops less than or equal to 541*F
What is the function of the P-12 Status light being on?
- Allows manual block of SI due to Low Steam Line Pressure 2. Coincident w High Steam Flow, will give MSI 3. Blocks all Steam Dump Valves
What condition will make the P-12 Status light off?
3/4 Loop Tavgs > 541*F
What is the function of the P-12 Status light being off?
Prevents or defeats manual block of SI due to low steam line pressure
What condition will make the P-13 Status light on?
2/2 Turbine 1st stage pressures <10% equivalent
What is the function of the P-13 Status light being on?
Input to P-7
What condition will make the P-13 Status light off?
1/2 Turbine 1st Stage pressures > 10%
What is the function of the P-13 Status light being off?
Input to P-7
What condition will make the P-14 Status light “on”?
2/3 SG NR levels < 64% in all 4 SGs
What is the function of the P-14 Status light being “on”?
Allows main feed water addition to SGs
What condition will make the P-14 Status light “off”?
2/3 SG NR levels > 67% in at least 1 SG
What is the function of the P-14 Status light being “off”?
Prevents Main Feedwater addtion to the SGs by initiating a FWI and tripping both MFP turbines and the main turbine
Which Permissives are normally lit at 100% Power?
P6 and P10
What are the “at power trips” that reaching P7 permites the auto block of?
PZR Press Low
PZR Level Hi
RCS Loss of Flow
UV RCP Busses
UF RCP Busses
RCP Breaker Position