Equipment Auto Starts Flashcards
What is the starting sequence for the Fire Pumps?
Motor Driven 140 psig for 2 sec
East Diesel 130 psig for 15 sec
West Diesel 120 psig for 25 sec
What are the EDG Starts?
CR Control Switch Local PB Loadshed SI Manual Starting Air Valves
What are the Circ Water Pump Auto Starts?
Failure of a running pump if in Auto
What are the ESW Pump Auto Starts?
- SI
- Loadshed
- Lo HDR Press 40 #s if in Auto
What are the CCW Pump Auto Starts?
- SI
- Loadshed
- Lo discharge pressure 80#s if in Auto
What are the auto starts for the PAC Aux Oil Pump?
- PAC Start (until pressure >42psi)
- PAC Stopped (15 mins)
- Low LO Press
- Loss of DCCS Control Power
- Plant Air HDR 97#
What are the Glycol Pump Auto Starts?
Low Discharge Pressure 95 #s
What are the CTS Pump Starts?
- Phase B
- Loadshed w/ Phase B
- Manual
What are the AES Fan Auto Starts?
- SI
2. ECCS / CTS Pump Start on that Train
What are the Auto Starts for the EDG Fans?
- EDG Start. Exhaust then 20 sec later Supply
2. 95*F room temperature
What are the auto starts for the ESW Room Fans?
- One starts on Pump Start
2. The other cycles on 90*F Room Temp
What will auto start the CCW Pump Fans?
Unit Specific Load Conservation
Unit 1: #2 and 3
Units 2: #1
What will auto start the control room pressurization fan?
- Either Unit SI
- Unit Specific High Control Room Radiation
- CR Cable Vault Fire
What will Auto Start a Heater Drain Pump?
NOTHING
What will Auto Start a Hotwell Pump?
Low Pressure 130 (110) #
What will Auto Start a Condensate Booster Pump?
Low Pressure 325 #
What will Auto Start a TACW Pump?
Low Discharge Pressure 155 (145) #
What will Auto Start the MDAFPs?
- Both MFPs Trip (only in auto)
- AMSAC
- Loadshed
- Lo-Lo SG 2/3 on 1 SG 5% (22%)
- SI
What will Auto Start the TDAFP?
- Undervoltage on RCP Bus (1/2 on 2/4 Busses) @ 88 V
- SG Lo-Lo 2/3 on 2 SGs @ 5 (22)%
- AMSAC
What will auto start the Stator Water Pump in U1?
Low Pressure at 120#
What will auto start the Stator Water Pump in U2?
- Low Pressure at 80#
2. Low Flow 845 gpm
What will auto start the U1 Emergency Seal Oil Pump?
MSOP Disch Press < 125 #
What will auto start a Charging Pump?
SI
Loadshed with SI
What is the MFP Seal Water pp Auto Start?
Booster Pump discharge vs MFP Suction pressure < 15 psid
What will autostart the U1 bearing lift pumps?
low speed switch
When will U1 bearing lift pumps 2 and 4 start?
20 secs after turning gear engagement to ensure sufficient drag
When will the U2 bearing lift pumps auto start?
Turbine trip
When does the U2 Main turbine turning gear auto start?
1 min after turbine trip
What will auto start the RHR Pumps?
SI
Loadshed with SI
What will put an AES Fan in Charcoal Mode?
- Phase B
- CS in Stop (only that fan)
- Loss of power to either fan
- Loss of CA
What will auto start the standby WGC?
high vent header pressure of 2 #
stops when below 1.3 PSIG