CCW Flashcards
What are the CCW Pump auto starts with the pump switch in auto?
- Load Shed
- SI
- Low discharge # @ 80#
What are the CCW Pump auto starts with the pump switch in neutral?
- Load Shed
- SI
What are the CCW Pump trips?
- Load shed
- Overload
- Overcurrent
What are the CCW Safeguards loads?
- RHR Hx
- RHR pp Seal Hx
- CTS pp Seal Hx
- SI pp LO Cooler and Seal Hx
- CCP LO cooler and Speed Increaser
What are the CCW Misc loads?
- SFP Hx - #1 load
- Letdown Hx
- Excess Letdown Hx
- RCP LO and Thermal Barrier Hx
- RCP Seal Water Hx
- CEQ Fan Motor Air Coolers
- WGC
- Reactor Vessel Support Coolers
- Cnt Penetration Coolers
- Sample HXs
- NBAE
- MS Penetration Coolers
- Recip CP
- Hydrogen Monitor
- PACHMAS
- Recip Charging
What are the Phase “A” actions for CCW?
- SFP Hx Isolates
- XS LD Hx Isolates
- Reactor Support Cooler Isolates
- NBAE Isolates
What are the Phase “B” actions for CCW?
- RCP Cooling Isolates
(Thermal Barrier and Lube Oil coolers) - Requires Manual Trip of RCPs within 3 mins
What are the SI actions for CCW?
- CCW Hx Outlet Opens (also open on LOOP)
- CCW Outlet Valves for RHR Hx Open to 3000-3500 gpm
- ESW to CCW Hx throttles to 5000 gpm
- Letdown Hx Isolates
What are the power supplies for the CCW pumps?
- T11/21A West CCW Pump
- T11/21D East CCW Pump
What power supply does the Spare CCW pump use?
Utilizes controls and power supply of pump being replaced
How tall is the baffle plate in the CCW Surge Tank?
5 feet high
(48” indicated)
Does the surge tank have any auto makeup?
No!
When will the CCW Surge tank vent valve (CRV-412) auto close?
CCW high rad signal
What protects the CCW surge tank if the vent valve is closed?
Safety valve and vacuum breaker
How do the demin water makeup water valves (CRV-410/411) fail?
Closed
on both loss of air and loss of 250 vDC
How many Gallons per inch in the CCW Surge Tank?
69 gal per inch
What is the purpose of the CCW tank Baffle?
Provides train separation and redundancy for passive failure during recirculation phase of LOCA
What is the purpose for the Cntmt Penetration Coolers?
Prevent concrete from drying out and cracking (spalling)
What is the purpose of the RCP Thermal Barrier safety ?
Lifts at 2485# and allows for controlled shutdown
When will the CCW Hx outlet valves open?
- SI
- LOOP
Are the CCW HX Valves credited to open on a LOOP?
No
How many CCW Trains are required to be Operable in Modes 1-4?
2 CCW Trains required
Restore w/in 72hrs
What happens to CCW System when Cntmt pressure reaches 1.0 psig?
CEQ fan motor cooler CIVs open
What does the CCW Hx Outlet Valve throttle flow to on an SI signal?
Full open
Why is there one line from CCW to the RCPs, and two lines coming out for the return from the RCPs?
So we can isolate the thermal barrier if it leaking from the RCS
Why do the CCW for the main steam penetrations not close on a Phase A?
Still have steam through it
If the CCW low pressure alarm comes in and the CCW pump motor instant trip alarm is standing and neither CCW pump is running can you start a CCW pump?
Yes, as long as the control switch is not taken to trip, which would reset the anti-pump circuit
If an individual load is isolated on the miscellaneous header of the CCW System (SFP Hx), is CCW still OPERABLE?
YES! as long as it can still do it’s safety related function.
The component isolated may be INOPERABLE
If an individual load is isolated on the CCW System (RHR Hx), is CCW still OPERABLE?
NO!
The RHR Hx is required for the safety function of the CCW system, to cool water from the recirc sump during the recirc phase. Without the RHR heat exchanger flow minimum flow for the CCW pumps may not be attainable during the injection phase.
What happens to The CCW Hx Outlet valves (CMO-410/420) on a Load Shed?
Gets an open signal on the blackout