Equipment Trips Flashcards
What are the Diesel Fire Pump Trips?
- Engine Cranks for 6 15-sec cycles then stop
2. Engine Overspeed 2112 RPM
What are ALL the EDG Trips?
BIG C FLANGE
B earing Temp Hi I ncomp Start G enerator Phase Overcurrent C 02 Actuation F uel Oil Pressure Low L ube Oil Pressure Low A ir Chest Pressure Hi N eutral Overcurrent G enerator Phase Diff E lectronic Overspeed
What are the EDG Trips if the EDG is actually needed?
GEM
G enerator Phase Diff
E lectronic Overspeed
M anual PB
What are the EDG Trips with 250 VDC Unavailable?
Worthington
Mech Overspeed
What will Trip a Circ Water Pump?
Undervoltage on Associated 4 KV Bus
What will trip the SFP Pump?
Load Cons
Load Shed
Overload / Overcurrent
What are the CAC Trips?
Does NOT Loadshed
Low Oil Pressure
Low NESW Pressure
Overload
What are the PAC Trips?
Loadshed
Load Cons
Overload
What trips the AS/AX and AFS/AFX Fans?
Load Conservation
What are the Heater Drain Pump Trips?
- Lo-Lo Level in Suction Heater
- Turbine Trip
- Overload / Overcurrent
- Both Suction Valves FULL CLOSED (M HDP only)
If the Unit Emergency Trip PB is pressed, what is the only DIRECT result?
HEAs open
What are the U1 Turbine Trips?
ASS MOISTURE COOLL
A MSAC S I S team Gen Level Hi-Hi 67% M anual O verall HEA I OPS 110% S tator Cooling Water (10 sec Delay) Lo Press 13 # Lo Flow 195 gpm Hi Temp 95*C (+ 5 sec delay) T hurst Bearing Wear Abnormal U nit HEA R eactor Trip E mergence Trip
C ondenser Vac O verspeed 107% Oil Pressure < 8 psig > 5 sec L o EHC HDR Press L o Trip HDR Press
What are the U2 Turbine Trips?
ASS MOISTURE COOLL
A MSAC S I S team Gen Level Hi-Hi 67% M anual O verall HEA I OPS 110% S tator Cooling Water (10 sec Delay) Lo Press 28 # Lo Flow 666 gpm Hi Temp 95*C (+ 5 sec delay) T hurst Bearing Wear Abnormal U nit HEA R eactor Trip E mergence Trip
C ondenser Vac O verspeed 107% Oil Pressure < 14.7 psig > 5 sec L o EHC HDR Press L o Trip HDR Press
What is the Low Oil Pressure Turbine Trip for U1?
Oil Pressure < 8 psig > 5 sec
What is the Low Oil Pressure Turbine Trip for U2?
Oil Pressure < 14.7 psig > 5 sec
What are the MFP Trips?
MR. SHIT COOLL
M anual R eactor Trip S I H i-Hi SG Level (P-14) I OPS (110%) T hurst Bearing Wear C ondenser Vac Low O il Pressure Low O verspeed 107% L ow Suction Pressure L ow Trip Hdr Pressure
RHR Pump will trip on low-low level of what?
9% Level in RWST IF RHR suction valves (IMO-310 and 320) are not fully closed.
What would cause the Unit specific Release Valve RRV-287 or RRV-286 to Trip?
Loss of all Circ Water Pumps for your Unit
What would cause the Liquid Release Valve RRV-285 to Trip?
RRS-1001 Hi Rad
RRS-1000 Failure
High/Low Rad Monitor Sample Flow on RFS-1010
What would Trip off a Monitor Tank Pump?
If in RELEASE:
RRS-1001 Hi Rad
RRS-1000 Failure
High/Low Rad Monitor Sample Flow on FRS-1010
When proper tank selected:
Low Monitor Tank Level
What will trip the WGC?
Low Moisture Sep Pressure - 25#
Load Cons
< 0.5 #
What will close the inlet to the I/S GDT ?
Hi-Hi Oxygen at 2.7% from AOM.
100# on I/S Tank
Swaps to Standby GDT if 1 is selected
What will trip closed the Waste Gas Release Flow Control Valve RRV-306?
Loss of both U1 Aux Exhauste Fans
Hi Rad on U1 or U2 Vent Stack Rad Monitors
What will trip the Rod Drive MG Supply Breakers?
Load Cons
Overcurrent
What will trip the Rod Drive MG Output Breakers?
Overvoltage
Overcurrent
Reverse Current
Supply Breaker Open