Oily Waste and Non-Radioactive Waste System Flashcards

1
Q

What is the purpose of the OW system?

A

Collect and transport liquid waster from equipment and floor drains in the turbine building, control building, diesel building, fire pump house and yard area

collection point for an oil/water mixture at the oily waste separator where the oil is manually skimmed and removed for proper disposal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How many sump pumps are utilized in the sumps of the OW system?

A

2 each

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of the alternator?

A

Swap lead pumps to equalize run time and wear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Why is there flow orifices installed in the discharge of the sump pumps?

A

to balance flow to control pump runout during one or two pump operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What system provides lube to the control building sump pumps intermediate and case bearing?

A

Demin water (DW)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What system provides lube to the DG building sump pumps?

A

Domestic service (DS)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What starts and stops the sump pumps on high or low level?

A

Float level control switches (first set for control and second for alarm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The turbine building OW system sump pumps normally send waste to oil/water separator. Where else can waste be sent?

A

CWNT or LRS holdup tanks if there are chemicals or radioactivity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is the water from the battery room in the switchgear building directed?

A

Acid neutralizing sump in the room and then to the north condenser sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Generally what type of water is collected in the turbine building sumps?

A

Water with the highest potential for water being present

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What waste is received in the North condenser area sump?

A

North and west areas of the turbine building and the CST pump house

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What drains are collected in the West control building sump?

A

‘A’ train side of the control building
‘A’ & ‘B’ EW heat exchanger tube side drains

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What drains are collected in the East control building sump?

A

‘B’ train side of the control building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is different about the waste from the ‘A’ and ‘B’ cable spreading rooms?

A

They do not flow to the control building sumps

They drain separately to the ground outside the control building

Drain screens on the outlets of the 2 drains

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What collects in the east and west diesel building sumps?

A

Their respective diesel leakage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What drains are received in the yard area sump?

A

Demin water storage tank and pumps

Aux boiler (no longer used)

Turbine building normal air handling units

17
Q

Where do the yard area sumps discharge to?

A

CW canal

18
Q

What is the capacity of the retention tanks?

A

505,000 gallons

19
Q

Where are the retention tanks located?

A

plant west of the unit 3 spray pond

20
Q

What is the purpose of the retention tanks?

A

Receive effluent from all 3 units turbine building OW separators and Chem waste neut tank transfer pumps

21
Q

Who operates the retention tanks?

A

Water resources

22
Q

At what level will a sump pump start to pump its associated sump?
When does the 2nd start?
What level do they secure?

A

80% level to start
90% for the 2nd
20% they stop