Fire Protection Flashcards

1
Q

What are the 3 sub systems of FP?

A

Fire protection - Chemical
Fire protection - H20
Fire detection and alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the functions of the fire protection chemical system?

A

Detect, contain and extinguish all fires in areas where water is impractical

minimize loss of life and property

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the functions of the fire protection h20 system?

A

Maintain a reliable source of water to fight and extinguish fires

provide water flow and pressure to supply the requirements at hose hydrants for manual firefighting

provide water flow and pressure required when wet pipe and/or pre action sprinkler systems are activated by fire detection equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the functions of the fire detection and alarm system?

A

provide fire/smoke detection capability in all plant areas that have the potential to expose safety related equipment to fire

Initial visual and audible alarms to warn plant personnel of a fire/smoke condition

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are some of the properties that make C02 a desirable extinguishing agent?

A

(CCR)
Non-combustible
Non-conductive
Non-reactive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How does C02 extinguish fires?

A

Suffocation and cooling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What areas are protected by the fire protection C02?

A

Battery rooms A-D
ESF switch gear rooms A & B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How is C02 flooding initiated?

A

When one smoke and one thermal detectors are actuated

The first alarm (a bell) actuates when one detection zone actuates

The 2nd alarm will be the pre discharge alarm for personnel to evacuate the area

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What would you need in order to use a C02 hose reel?

A

SCBA and turnout gear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the source of the C02?

A

Cardox unit (also supplies steam generator purge)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the properties of Halon?

A

(TLC)
Non-toxic
Leaves little residue
non-conductive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What areas are protected by halon?

A

Remote shutdown room
inverter room
computer room
communications room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Number of halon containers in each space is determined by what?

A

Volume of space

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens upon an activation of halon?

A

1st detector alarms to allow personnel to evacuate

2nd Isolates the room from the HVAC system and discharges entire bottle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

In regards to FP - water system, how many pumps are there and their capacity?

A

Three 50% fire pumps along with a jockey pump that maintains header pressure with no loads on the system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How far apart are hydrants placeds?

A

250 feet

17
Q

Where are the 2 water storage tanks located?

A

Water resources

18
Q

How are the fire hose stations situated?

A

all over in 75 foot lengths and special permissions at 100’ when necessary

19
Q

What are the 3 types of sprinkler systems?

A

Wet pipe
Pre-action
Deluge

20
Q

PNVGS fire zones are identified in what manual?

A

Pre-fire strategies manual

21
Q

What are the different types of fire detectors?

A

Ionization detector
Photoelectric detector
Ultraviolet detectors
Heat actuated devices
Line type detectors

22
Q

What supplies power to the local CO2 fire control panels?

A

Essential lighting (QB)

23
Q

What system maintains level in the fire water storage tanks?

A

Domestic service water (DS)

24
Q

How is IA utilized in the FP system?

A

Pre-action sprinklers use 20psig of service air to monitor integrity of the dry fire water piping