Auxiliary Feedwater System Flashcards

1
Q

What is the Basis for the amount of AF that is reserved for use in the plant during emergency situation?

A

Provides sufficient reserve of feed water to permit the plant to operate in mode 3 for 8 hours followed by an orderly plant cool down rate not to exceed 75F/HR to the point where shutdown cooling may be placed in operation (RCS temp 350F)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the capacity of the CST and RMWT?

A

CST 550,000

RMWT 480,000

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is HA affected by a high water level in either AF pump room?

A

Aux building AHU dampers isolate the rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is ‘N’ AFP self lubricating?

A

Uses dipper rings to throw oil onto the bearings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What provides cooling water for AFP lube oil coolers?

A

Pump first stage discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where is AF ‘N’ powered from?
Control power?

A

PBA-S03

Control power - has 2 sources PKA-D21 and ‘A’ battery charger

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Why does the AF ‘N’ have 2 class powered suction valves?

A

Provide class and seismic protection boundary for CST inventory, separating it from the non-seismic piping to AF ‘N’ downstream isolation valves. (CTA-HV-4 & CTA-HV-111)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where are the AF ‘N’ class power valves located and what is there designation?

A

CST pump house (CTA-HV-4 & -1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the interlock associated with AF ‘N’ and its suction valve? What is the purpose?

A

If either valve (CTA-HV-4 & -1) is less than 80% open then the pump will not start and will trip if running

Purpose is to provide protection from a low suction pressure condition, which could damage the pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Where are all the non-seismic penetrations located on the CST?

A

Above the safety storage volume of 330,000 gallons or 29.5 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the difference between AF ‘N’ and ‘B’ even though they are similar pumps?

A

‘B’ designed to meet seismic requirements

‘B’ equipped with a larger horsepower motor (125% larger)

‘B’ equipped with auto start feature from the ESFAS load sequencer module of the BOP ESFAS that will start under certain conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What happens when the AF ‘B’ ‘A’ start?

A

Essential air cooling unit auto starts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the purpose of the AF ‘A’ worm drive gearbox?

A

Coupled to an oil pump and the turbine governor actuator and driven off the turbine

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What provides cooling water to the AF ‘A’ lube oil cooler?

A

First stage of the AFP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum speed of AF ‘A’ pump to provide adequate lube and cooling?

A

1000rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How do we maintain the cleanliness of the AF ‘A’ governor control system?

A

Renewable cartridge filter that has a built in dirt alarm that will auto bypass the filter when it becomes clogged

17
Q

How does the AF ‘A’ respond to AFAS?

A

SGA-UV-134A and -138A open first to bring the turbine up to speed in a slow and controlled manner

30 seconds later SGA-UV-134 and 138 open to allow maximum steam flow to the turbine and as the turbine approaches nominal speed, governor begins to throttle governor control valve to 3600 rpm

18
Q

Why is there a large condensate pot installed in the Aux Building?

A

To allow constant draining of moisture that accumulates in the steam supply line

Without it moisture could accumulate in the steam supply line and greatly increase the chance of turbine overspeed during startup

19
Q

Where can I trip AFA-HV54 electrically?

What is AFA-HV54?

A

Board 6 in the control room

‘A’ remote shutdown panel

local control panel

It is the steam supply valve to the ‘A’ AF turbine AFA-k01

20
Q

What is a trip of AFA-HV-54?

A

Mechanical overspeed device

21
Q

What is the purpose of the AF regulating and isolation valves?

A

Provides means to regulate and isolate flow, respectively to the steam generators from the essential AF pumps

22
Q

What powers the regulating and isolation valves associated AF ‘A’?

A

PKA and PKC

23
Q

What is pressure locking in regards to double disk gate valves?

A

When a valve is closed and water gets trapped and thermal expansion locks the valve

24
Q

How do we prevent pressure locking?

A

Each ‘A train isolation babes bonnet area is connected to a relief valve that relieves to the CST, normally via ‘A’ AFP mini-flow line

‘B’ has an equalizing valve on the bonnet and discharges to the side of these valves

25
Q

What happens when an AFAS is received and what initiates it?

A

Generated by PPS when applicable steam generator water level has lowered to 25.8%

Both Essential AF pumps start and affected SG regulating and isolation valves open

When level in the SG reaches 40.8% the applicable regulating and isolation valves are open

26
Q

What happens if SG pressures differ by more than 185psid?

A

The DP lockout will close the regulating and isolation valves for the affected SG and prevent them from being reopened

27
Q

What is the power supply of AF ‘B’?

A

PBB-S04

28
Q

During startup, up to what power will we maintain SG levels with AF?

A

2%