RC monitors all interchange transactions into, out of, or through the area. Also responsible for making info available to:
All RC’s in the interconnection.
If an RC detects a frequency error due to an external cause, what should they do?
Initiate a NERC hotline call to discuss the issue.
Can an RC request the time monitor to terminate a time error correction?
Can transmission owners, generator owners, or NERC?
Yes
No
Of the following entities, who does NOT have to report info to the RC for performing next-day studies? A. Transmission Operators B. BAs C. LSEs D. PSEs
D. PSEs
The RC's communication capabilities with its TO's and BA's and neighboring RCs must be: A. Redundant B. Digital C. Multi-directional D. Satelite
C. Multidirectional
An RC can only use local TLR or CM procedures when which of the following experiencing an SOL/IROL violation is a party to the procedures? A. TOP B. BA C. RSG D. GOP
A. TOP
RC must notify other RC’s in the interconnection when an EEA is declared at which level?
ALL. (There is no level 4)
Information in the ISN may be used by all of the following except: A. GOPs B. PSEs C. Intermediate BA's D. GO's
B. PSEs
Electric System SEcurity Data is received over the ____ and the data must be updated every _____
ISN; 10 min
Adjacent BA’s must use ____ MWh meters, with readings provided _____ to the CC’s of adj. BA’s
common; hourly
Each SOL/IROL violation shall be reported to the regional council and NERC compliance subcommittee within ____ hours
72