Main Steam Flashcards
Unit 1 is at 100% power with all systems in a normal lineup.
Power is lost to PKA-M41.
How many ADVs can be operated from the control room?
A. 0
B. 1
C. 2
D. 4
C
Unit 2 is at 100% power with all systems in a normal lineup.
Power is lost to PNB-D26.
How many ADVs can be operated from the control room?
A. 0
B. 1
C. 2
D. 4
C
Unit 1 is at 100% power with all systems in a normal lineup.
Power is lost to PND-D28.
How many ADVs can be operated from the control room?
A. 0
B. 1
C. 2
D. 4
D
Unit 3 is at 100% power with all systems in a normal lineup.
Power is lost to PKD-M44.
How many ADVs can be operated from the control room?
A. 0
B. 1
C. 2
D. 4
C
Unit 2 is at 100% power with all systems in a normal lineup.
Power is lost to PKA-M41.
With no operator action, ‘A’ train Economizer Isolation valves are ___(1)___, and ‘A’ train Downcomer Isolation valves are ___(2)___.
A. (1) open; (2) open
B. (1) open; (2) closed
C. (1) closed; (2) open
D. (1) closed; (2) closed
A
Which of the following does NOT close on a MSIS?
A. Steam Generator Sample valves
B. AFW pump ‘A’ steam admission valves
C. MSIV bypass valves
D. Chemical Injection Isolation valves SGB-HV-200 & 201
B
Which ESFAS signals will close Main Steam System Chemical Injection Isolation valves SGB-HV-200 and SGB-HV-201? A. SIAS & MSIS only B. SIAS & CIAS only C. CIAS & MSIS only D. SIAS, CIAS, & MSIS
C
Downcomer Block Valve SGN-HV-1142 is operated by ___(1)___ and fails ___(2)___.
A. (1) a motor powered from NHN-M02; (2) as is
B. (1) a motor powered from NHN-M71; (2) as is
C. (1) instrument air; (2) open
D. (1) instrument air; (2) closed
B
Downcomer Bypass Valve SGN-HV-1143 is operated by ___(1)___ and fails ___(2)___.
A. (1) a motor powered from NHN-M02; (2) as is
B. (1) a motor powered from NHN-M71; (2) as is
C. (1) instrument air; (2) open
D. (1) instrument air; (2) closed
B
Total steam flow leaving the steam generators at 100% power is closest to: A. 5,000,000 lbm/hr B. 9,000,000 lbm/hr C. 15,000,000 lbm/hr D. 18,000,000 lbm/hr
D
MSIV logic power is normally supplied from: A. Class batteries B. Class 125 VDC buses C. Class 120 VAC buses D. Class 480 VAC buses
A
Main Steam Safety Valves are designed for \_\_\_(1)\_\_\_ accumulation and \_\_\_(2)\_\_\_ blowdown. A. (1) 1%; (2) 1% B. (1) 1%; (2) 3% C. (1) 3%; (2) 1% D. (1) 3%; (2) 3%
B
The normal motive force for an ADV operated from the control room is: A. a motor B. hydraulic oil pressure C. Instrument Air D. a nitrogen accumulator
C
Which of the following parameters will cause a MSIS?
A. Containment Pressure of 4 psia
B. Steam Generator Pressure of 950 psia
C. Steam Generator Wide Range Level of 40%
D. Steam Generator Narrow Range Level of 90%
B
Draw the Main Steam System.
-1. You didn’t list the normal system pressures.