Main Generator Flashcards
What are the modes of operation of the voltage regulator?
OFF - manual (DC adjuster)
TEST - manual (DC adjuster). AC adjuster gets power, but is not controlling
ON - auto (AC adjuster)
How does the voltage regulator operate in auto mode (AC adjuster)?
Senses generator voltage (terminal voltage) and maintains it at setpoint
How does the voltage regulator operate in manual mode (DC adjuster)?
- Senses exciter field and compares it to a reference signal (set by the operator in the control room) and tells firing circuit when to fire (raise/lower field excitation)
- No limiters while in manual.
- Manual tracks auto for bumpless transfer.
How does the voltage regulator, exciter, and generator work to produce voltage to be sent to the grid?
- PMG on rotor induces a voltage that is sent through the field breaker to power the voltage regulator.
- Voltage regulator looks at terminal voltage and outputs a DC voltage to the exciter field windings.
- Exciter field induces a voltage on the rotor in the exciter.
- This voltage is rectified to DC, which is supplied to the windings on the rotor in the generator.
- DC voltage in the rotor windings induces a voltage (22 KV) on the stator in the generator.
- 22 KV from the stator is then sent to the main transformer, where it is transformed to 345 KV and sent to the grid.
What is the purpose of the permanent magnet generator?
Provides power to the voltage regulator for field excitation
What is the purpose of the exciter?
Provides current to the rotor field
What is the purpose of the rectifier wheels?
Turns AC current from the exciter to DC current to be supplied to the main generator field windings on the rotor.
What is the required response to blown fuses on the rectifiers?
- 1 fuse blown - contact system engineer
- 2 fuses blown for 1 phase - shutdown within 24 hours and monitor every 4 hours
- 3 fuses blown for 1 phase - < 15% power, trip the turbine. > 15% power, trip the reactor
What is the purpose of the field breaker?
Connects the PMG to the voltage regulator
What happens if the field breaker is opened while at power?
Loss of excitation alarm and 386P relay actuates, which will trip the plant
What is the process for transferring the voltage regulator from manual to auto?
- Take voltage regulator switch to test
- Match output of the AC and DC adjusters by ensuring regulator balance meter is at 0. Accomplished by raising/lowering AC adjust switch
- Once regulator balance meter is at 0, take voltage regulator switch to on
What is the function of the 386P/B relays?
Trips the turbine/generator on electrical faults that would make you not want to use the coast down feature.
What happens when the 386P/B relays actuate?
- Turbine trip
- Generator trip
- Exciter trip
- Fast transfer of electrical buses to startup power immediately
What is the function of the 386C relay?
Trips the turbine/generator on non-electrical faults that you would want to use the coast down feature.
What happens when the 386C relay actuates?
- Turbine trip
- Generator trip
- Exciter trip
- Fast transfer of electrical buses to startup power after 10 seconds