What are the modes of operation of the voltage regulator?

A

OFF - manual (DC adjuster)
TEST - manual (DC adjuster). AC adjuster gets power, but is not controlling
ON - auto (AC adjuster)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How does the voltage regulator operate in auto mode (AC adjuster)?

A

Senses generator voltage (terminal voltage) and maintains it at setpoint

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How does the voltage regulator operate in manual mode (DC adjuster)?

A
  • Senses exciter field and compares it to a reference signal (set by the operator in the control room) and tells firing circuit when to fire (raise/lower field excitation)
  • No limiters while in manual.
  • Manual tracks auto for bumpless transfer.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does the voltage regulator, exciter, and generator work to produce voltage to be sent to the grid?

A
  • PMG on rotor induces a voltage that is sent through the field breaker to power the voltage regulator.
  • Voltage regulator looks at terminal voltage and outputs a DC voltage to the exciter field windings.
  • Exciter field induces a voltage on the rotor in the exciter.
  • This voltage is rectified to DC, which is supplied to the windings on the rotor in the generator.
  • DC voltage in the rotor windings induces a voltage (22 KV) on the stator in the generator.
  • 22 KV from the stator is then sent to the main transformer, where it is transformed to 345 KV and sent to the grid.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the purpose of the permanent magnet generator?

A

Provides power to the voltage regulator for field excitation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the purpose of the exciter?

A

Provides current to the rotor field

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the purpose of the rectifier wheels?

A

Turns AC current from the exciter to DC current to be supplied to the main generator field windings on the rotor.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the required response to blown fuses on the rectifiers?

A
  • 1 fuse blown - contact system engineer
  • 2 fuses blown for 1 phase - shutdown within 24 hours and monitor every 4 hours
  • 3 fuses blown for 1 phase - < 15% power, trip the turbine. > 15% power, trip the reactor
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the purpose of the field breaker?

A

Connects the PMG to the voltage regulator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens if the field breaker is opened while at power?

A

Loss of excitation alarm and 386P relay actuates, which will trip the plant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the process for transferring the voltage regulator from manual to auto?

A
  • Take voltage regulator switch to test
  • Match output of the AC and DC adjusters by ensuring regulator balance meter is at 0. Accomplished by raising/lowering AC adjust switch
  • Once regulator balance meter is at 0, take voltage regulator switch to on
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the function of the 386P/B relays?

A

Trips the turbine/generator on electrical faults that would make you not want to use the coast down feature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What happens when the 386P/B relays actuate?

A
  • Turbine trip
  • Generator trip
  • Exciter trip
  • Fast transfer of electrical buses to startup power immediately
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the function of the 386C relay?

A

Trips the turbine/generator on non-electrical faults that you would want to use the coast down feature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens when the 386C relay actuates?

A
  • Turbine trip
  • Generator trip
  • Exciter trip
  • Fast transfer of electrical buses to startup power after 10 seconds
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the function of the minimum excitation limiter?

A
  • Only works with AC adjuster

- 21.7 KV minimum excitation

17
Q

What is the function of the loss of field relay?

A
  • Caused by voltage regulator malfunction, or opening of the field breaker
  • Plant trip on 386P
18
Q

What is the function of the volts/Hz limiter?

A
  • Limits terminal voltage to 23.1 KV
  • Only works with AC adjuster
  • If limiter fails to retard voltage, at 23.54 KV plant trips on 386P
19
Q

What is the function of the maximum excitation limiter?

A
  • Limits field current to 273 amps

- Only works with AC adjuster

20
Q

What is the function of the regulator over excitation module?

A
  • 283 amps field current for greater than 33 seconds, then voltage regulator swaps to manual
  • If problem persists for more than 3 seconds after swap to manual, plant trips on 386P
21
Q

What is the purpose of the stator coil hot gas temperature PPC alarm?

A
  • alarms at 8 C differential temperature

- indicates a hot spot in the stator, and there may be generator damage

22
Q

What is the consequence of high cold gas temperature?

A

Reduces the life of gaskets and seals, and eventual H2 leak