CRHVAC Flashcards
LCO 3.7.10 “Control Room Ventilation (CRV) Filtration” requirement
2 CRV Filtration trains shall be operable
LCO 3.7.10 “Control Room Ventilation (CRV) Filtration” required actions if 1 or more CRV Filtration trains inoperable due to inoperable C.R. Envelope boundary in Modes 1-4
Initiate action to implement mitigating actions IMMEDIATELY.
LCO 3.7.10 “Control Room Ventilation (CRV) Filtration” required actions if 2 CRV Filtration trains inoperable during core alterations, movement of irradiated fuel assemblies, or during movement of a cask over the SFP
Suspend core alterations, stop movement of irradiated fuel assemblies, stop movement of cask over the SFP IMMEDIATELY
LCO 3.7.10 “Control Room Ventilation (CRV) Filtration” required actions if 1 or more CRV Filtration trains inoperable due to inoperable C.R. Envelope boundary during core alterations, movement of irradiated fuel assemblies, or during movement of a cask over the SFP
Suspend core alterations, stop movement of irradiated fuel assemblies, stop movement of cask over the SFP IMMEDIATELY
LCO 3.7.10 “Control Room Ventilation (CRV) Filtration” required actions if 2 CRV Filtration trains inoperable for something other than C.R. Envelope boundary in modes 1-4
Initiate action to implement mitigating actions IMMEDIATELY.
LCO 3.7.11 “Control Room Ventilation (CRV) Cooling” requirement
2 CRV cooling trains shall be operable
LCO 3.7.11 “Control Room Ventilation (CRV) Cooling” required actions if 2 CRV Cooling trains inoperable during core alterations, movement of irradiated fuel assemblies, or during movement of a cask over the SFP
Suspend core alterations, stop movement of irradiated fuel assemblies, stop movement of cask over the SFP IMMEDIATELY
LCO 3.7.11 “Control Room Ventilation (CRV) Cooling” required actions if One CRV Cooling train inoperable and completion time not met during core alterations, movement of irradiated fuel assemblies, or during movement of a cask over the SFP
Place operable CRV cooling train in operation IMMEDIATELY
or
Suspend core alterations, stop movement of irradiated fuel assemblies, andstop movement of cask over the SFP IMMEDIATELY
When is CRHVAC recirc mode used
When outside air may have smoke or other gas that would make the C.R. uninhabitable
What functions are lost when CRHVAC is in recirc mode
C.R. envelope positive pressure.
RIA’s aren’t in the flow path, therefore will not be able to detect adverse radiological conditions.
Whose permission is needed to put CRHVAC in recirc mode
Shift Manager or Site Emergency Director
When is CRHVAC purge mode used
Used to clear C.R. of smoke or other gases.
What actuates CRHVAC emergency mode
Manual - 1 side actuates
Automatic (CHP/CHR) - both sides actuate
How does CRHVAC respond to a loss of D-11A/21A
CRHVAC fails to emergency mode.
VC-11/10 trips and will not restart.
How does CRHVAC respond to a loss of Y-10/20
Can’t be operated in emergency mode.
Fails to recirc mode.
VC-11/10 trips and will not restart.
Where can V-95/96 be operated from
Control Room or locally at C-186A/B (in CRHVAC rooms)
V-95/96 Control Room handswitch positions
On - starts unit and aligns the dampers for normal mode.
Auto - Starts unit on CHP/CHR after a 1 minute time delay.
Off/Reset - Secures unit and aligns dampers. Resets load shed circuitry if fan was not started by sequencer.
V-95/96 C-186A/B handswitch positions
Off - stops the unit
Remote - normal position
On - starts the unit and aligns dampers for normal mode
V-95/96 filter High DP alarm
0.75” H2O
VC-10 power supply
MCC-25
VC-11 power supply
MCC-26
VC-10/11 cooling water supply
Critical Service Water
Operation of CV-1655/1666, Condensing Unit VC-11/10 Service Water
As temperature increases, valve modulates open to lower condenser temperature and pressure.
How does CV-1655/1666, Condensing Unit VC-11/10 Service Water, fail
Valves fail open, which causes condenser temperature and pressure to lower to the point of a low suction pressure trip.
VC-10/11 handswitch positions
Off/Reset - turns unit off, resets load shed logic to allow starting, resets CHP/CHR logic for VC-10/11 (signal stays locked in after CHP/CHR reset)
Auto - Starts VC-10/11 when its associated AHU (V-95/96) starts after a 45 second delay
OVRD-CHP/CHR - override to allow VC-10/11 to start with a CHP/CHR signal
What is indicated by the amber trouble light on the VC-10/11 handswitch
Shows that the unit has either tripped or is in alarm
VC-10/11 trips
high discharge pressure
high oil temperature
low suction pressure
low differential oil pressure
VC-10/11 alarms
Condenser high differential cooling water pressure
High vibrations
VH-13, CRHVAC Humidifier - Train A, power supply
MCC-79
VH-12, CRHVAC Humidifier - Train B, power supply
MCC-80
VH-12/13 water supply
Domestic water
VH-12/13 auto trips
V-95/95 shutdown V-26A/B start (minimize water into the charcoal filters) CHP/CHR High water level High humidity - 90%
VF-26A/B pre-filter purpose
protects the heater
VF-26A/B electric heater purpose and power supply
remove moisture to protect the charcoal filters
VHX-26A - MCC-25
VHX-26B - MCC-26
HEPA filter high dp alarm
2” H2O (1st hepa filter only)
Charcoal filter purpose
removes iodine
Charcoal filter temperature alarm
High temp alarm in C.R. at 220 F
Hi Hi local alarm light at 280 F is a positive indication of a fire
V-26A/B, emergency fan, power supply
V-26A - MCC-25
V-26B - MCC-26
Where can V-26A/B be controlled from
Control Room handswitch
Locally at C-186A/B (in CRHVAC rooms)
V-26A/B Control Room handswitch positions
Off - stops fan and repositions dampers
Auto - Fan starts 1 minute after CHP/CHR
On - starts fan and repostions dampers
V-26A/B C-186A/B handswitch positions
On - starts fan and repositions dampers
Auto - normal
Off - stops fan and repostions dampers
V-94, Control Room Purge Exhaust Fan, purpose
purge smoke/gas from C.R.
V-94, Control Room Purge Exhaust Fan, power supply
MCC-79
V-94, Control Room Purge Exhaust Fan, trip
trips on CHP/CHR (purge mode is blocked)
LCO 3.7.10 “Control Room Ventilation (CRV) Filtration” applicability
Modes 1-4, during core alterations, movement of irradiated fuel assemblies, and during movement of a cask over the SFP.
LCO 3.7.11 “Control Room Ventilation (CRV) Cooling” applicability
Modes 1-4, and during core alterations, movement of irradiated fuel assemblies, and movement of a cask in or over the SFP.