Circ Water Flashcards
Cooling tower pump normal indication
800 amps @ 40-45 psi discharge pressure
Cooling tower pump power supplies
P-39A - F bus
P-39B - G bus
Cooling tower pump start permissives
Condenser inlet waterbox full No standing pump trips Emergency stop button not pushed Lubrication water >8 gpm Waterbox inlet valve closed Pump discharge valve closed
What happens when C/T pump control switch is taken to start
Condenser inlet starts to open
Pump starts when condenser inlet is 33% open
Pump discharge valve starts to open to a preset throttle position (approximately 43%)
What happens when C/T pump control switch is taken to stop
Pump discharge valve starts to close
Pump trips when discharge valve gets to 33% closed
Pump discharge valve fully closes
What happens when C/T pump emergency stop push button is pushed
Immediately trips pump
Pump discharge valve closes fully
Control Room alarm
C/T pump seal and cooling water supply
Normally from filtered service water
Self sealing if filtered service water is lost
C/T pump seal/cooling water alarm
18 gpm
C/T pump trips
Differential current
Bus undervoltage
Ground current
Overcurrent
C/T pump discharge valves MO-5305/5306 functions
Control C/T basin level
Interlocks to open/close on pump start/stop
Won’t auto close if pump is tripped locally from the breaker
Waterbox inlet valves MO-5301/5302 interlock
Open on C/T pump start
Steps to take if waterbox inlet valve leakage is present
Operate the valve to flush the seat
Attempt to seat the valve
Drain the C/T
Dilution water pump power supplies
P-40A - C bus
P-40B - E bus
Dilution water pumps capacity
40,000 gpm
Dilution water pump trips
overcurrent
undervoltage
SIS (load shed)