EDG's Flashcards

1
Q

“LCO 3.8.3 - EDG’s auxiliaries” requirements

A

Stored fuel oil, lube oil, and starting air within limits, and both fuel oil transfer systems operable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

“LCO 3.3.5 - EDG’s undervoltage start” requirements

A

3 channels of Loss of Voltage Function and 3 channels of Degraded Voltage Function and associated logic channels for each EDG shall be operable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

EDG operability

A
Jacket Water and Lube Oil >90F
Lube Oil <205F
Air Start Pressure >95# but <175#
Starting Air Tank Pressure >215#
Service Water available
Generator/Engine protective relays in service
Over speed is latched
Output Breaker is racked in with control power available
In UNIT (not in PARALLEL)
Voltage Regulator in AUTO
Crankcase covers installed
EDG Room ventilation
Outside Air <85F one fan in-service
Outside Air >85F two fans in-service
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

EDG trips

A

Overspeed - 1060-1105 rpm
Overcrank - 10 sec, 10 psi jacket water, 120 rpm
Overcurrent - 824 amps
Low lube oil pressure - 40 psi
Low jacket water pressure - 10 psi for 45 sec
Generator differential

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

EDG breaker trips

A
Engine trp
Overcurrent - 824 amps
Generator differential
Safeguards fualt
Loss of excitation
Turbine trip with EDG on the bus
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Parameters to manually trip the EDG

A

Jacket water > 195 F

Lube oil > 205 F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

EDG Generator load ratings

A

2500 kw continuous

2750 kw for 2 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

EDG generator loading rates

A

50 kw initial load

500 kw increments with 5 minute hold time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

“LCO 3.8.3 - EDG’s auxiliaries” applicability

A

All modes, when associated EDG is required to be operable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

“LCO 3.3.5 - EDG’s undervoltage start” applicability

A

All modes, when associated EDG is required to be operable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the required action if 1 or more loss of voltage or degraded voltage functions per EDG is inoperable?

A

IMMEDIATELY declare EDG inoperable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Why is EDG load only reduced to 50 kw prior to opening the output breaker?

A

To ensure the EDG is not motoring

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the power supplies for P-18A/B?

A

P-18A - MCC 8

P-18B - MCC 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the power supplies for EDG control power?

A

D/G 1-1 - D-11A

D/G 1-2 - D-21A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the power supplies for the EDG air start compressors?

A

G1-1 (D/G 1-1) - MCC 1