Electrical Distribution Flashcards

1
Q

“LCO 3.8.1 - AC Sources - Operating” requirements

A

2 off-site sources available

2 EDG’s available

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the required action if 1 off-site source OR EDG is inoperable in modes 1-4?

A

Perform off-site source checks WITHIN 1 HOUR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the required action if 3 off-site sources are inoperable in modes 1-4?

A

IMMEDIATELY Enter LCO 3.0.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

“LCO 3.8.2 - AC Sources - Shutdown” requirements

A

1 off-site source (startup 1-2 counts) and 1 EDG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the required action if a required off-site source or EDG is inoperable in modes 5 or 6 or during movement of irradiated fuel assemblies?

A

IMMEDIATELY Declare affected required features with no off-site sources available inoperable

                        OR

IMMEDIATELY Stop core alterations, suspend irradiated fuel moves, stop all actions that add positive reactivity, and initiate action to restore off-site power source or EDG to operable status

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens to C/D bus on a loss of safeguards bus?

A

Fast transfer to Startup 1-2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens if C and/or D bus being supplied by its respective diesel, and the plant trips?

A

EDG output breaker opens, load shed, output breaker re-closes, and shutdown sequencer loads the EDG.
EDG doesn’t trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens on a 2400 volt bus overcurrent?

A

Trip and lockout incoming breakers

Lock out EDG output breakers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What happens on a 2400 volt bus ground?

A

Control Room alarm only. No automatic actions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens on a 2400 volt bus undervoltage?

A

Instantaneous (77% of rated voltage) - -Trip incoming breakers, Load shed bus, EDG Starts, EDG breaker closes, Shutdown Sequencer brings loads back one at a time

Sustained (93% of rated voltage) - Degraded Voltage, After .6 seconds EDG Starts, After an additional 6 seconds Under voltage condition still in feeder breakers open and EDG breaker closes, Shutdown Sequencer brings loads back one at a time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At what percent power are buses powered from startup vs station power and why?

A

Startup - less than 20%
Station - greater than 20%

Keeps coastdown feature enabled for as long as possible

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the generator coastdown feature?

A

prevents Generator output breakers from opening and fast transfer on a plant trip for 10 seconds to allow more time for RCP operation to aid in establishing natural circulation
Blocked when there is a fault on the main generator or transformer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What happens on a 4160 volt bus overcurrent?

A

When Supplied from Start Up Transformers - Trips Start up Power Feeders

When Supplied from Station Power Transformers - Trips Station Power Feeders, Block Fast Transfer, Block Manual closure of feeder breakers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens on a 4160 volt bus undervoltage?

A
  • Inverse time delay that when times out trips RCPs, Cooling Tower Pumps, and Condensate Pumps to prevent motor damage
  • Opens Station Power Feeders and prevents fast transfer and locks out bus to prevent connecting a source of supply to a faulted bus
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens on a station power transformer fault on phase differential?

A
  • Opens all feeder breakers from Station Power Transformers
  • Trips Plant (386B relay) – Opens 25F7 and 25H9 no coast down feature
  • Buses Fast Transfer to Startup Transformers
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What happens on a station power transformer fault on sudden pressure?

A
  • Deluge Actuates

- Control Room Alarm

17
Q

What happens on a startup power transformer fault on sudden pressure?

A
  • Deluge Actuates

- Control Room Alarm

18
Q

“LCO 3.8.1 - AC Sources - Operating” applicability

A

Modes 1-4

19
Q

“LCO 3.8.2 - AC Sources - Shutdown” applicability

A

Modes 5 and 6, or during movement of irradiated fuel assemblies