LOT 202.41 Radiation Monitoring Flashcards
- LOT 202.41 Radiation Monitoring*
- *
What does the different colors on RM-11 mean?
- White:*
- *Offline**
- (Placed by User)*
- Magenta:*
- *No Communication**
- (Bypassed/Power Failure)*
- Blue:*
- *Equipment Failure**
- *Loss of Sample Flow**
- Red:*
- *Alarm**
- Yellow:*
- *Alert**
- Cyan:*
- *Equipment Pre-Failure**
- Grey:*
- *Function being executed**
- Green:*
- *Normal**
Order of priority (White, Magenta, Blue, Red, Yellow, Cyan, Grey, Green)
- LOT 202.41 Radiation Monitoring*
- *
What monitors are adjacent-to-line monitors?
GWPS Low Range (RT-8031/8032)
MSL Dual Range (RT-8046 - RT-8049)
SGBD Dual Range (RT-8022 - RT-8025)
MSL N-16 (RT-8130 - RT 8133)
- LOT 202.41 Radiation Monitoring*
- *
What detectors are scintillation detectors?
Unit Vent (RT-8010)
- *Containment Atmoshpere (RT-8011)**
- Beta and Gamma*
Containment Purge (RT-8012/8013)
CR HVAC (RT-8033/8034)
FHB HVAC (RT-8035/8036)
MSL N-16 (RT-8130 - RT 8133)
MAB Area Monitors
(RT-8014 - RT-8018)
(RT-8029/8030)
- LOT 202.41 Radiation Monitoring*
- *
What monitors are noble gas monitors?
**Unit Vent Monitor (RT-8010B)** Wide Range (PAMS)
Containment Purge (RT-8012/8013)
CR HVAC (RT-8033/8034)
FHB HVAC (RT-8035/8036)
- LOT 202.41 Radiation Monitoring*
- *
What types of radiation are monitored by the Area Radiation Monitoring System? (ARMS)
Beta
Gamma
- LOT 202.41 Radiation Monitoring*
- *
What radiation detectors would be important for determining a LOCA IRC?
- *RCB Atmosphere (RT-8011)**
- Will isolate on CVI*
Containment Purge (RT-8012/8013)
RCB PAMS (RT-8050/8051)
RCB Area (RT-8052 - 8056)
Refueling Bridge (RT-8099)
- LOT 202.41 Radiation Monitoring*
- *
What detectors are solid state detectors?
Unit Vent Mid / High Range Detectors (RT-8010)
- LOT 202.41 Radiation Monitoring*
- *
Where can RM-11 be read from?
MCR
HP
TSC
Computer Room
- HP, TSC, and Computer room can only use “User Mode.” (Data Retrieval/acknowldeging alarms)
- MCR normally uses “Windows Supervisor Mode.” (Allows non-tech spec parameters to be monitored)
- “RM-11 Supervisor Mode” can only be used in MCR and requires password. (Allows changing of setpoints)
- LOT 202.41 Radiation Monitoring*
- *
What detectors are Ion chamber detectors?
MSL High Range (RT-8046 - RT-8049)
SGBD High Range (RT-8022 - RT-8025)
- LOT 202.41 Radiation Monitoring*
- *
What powers the N-16 primary-to-secondary leak detector cabinet?
DP-048A
Adjacent-to-line monitor and a scintillation detector (RT-8130 - RT-8133)
Reads in GPD.
- Note:*
- Detector becomes very unreliable at low powers.*
- LOT 202.41 Radiation Monitoring*
- *
What monitor is a PI monitor?
Unit Vent Monitor (RT-8010A)
Only 1 per unit.
- LOT 202.41 Radiation Monitoring*
- *
What monitors are PIG monitors?
Containment Atmoshpere (RT-8011)
- *MAB Area Monitors**
- (RT-8014 - RT-8018)*
- (RT-8029/8030)*
- LOT 202.41 Radiation Monitoring*
- *
What systems have in-line liquid radiation monitors?
- *BRS (RT-8037)**
- Evaporator Condensate*
- *LWPS (RT-8038/8045)**
- Discharge / Process Liquid*
- *CVCS (RT-8039)**
- Failed Fuel Monitor*
CCW (RT-8040)
TGB Drains (RT-8041)
Condensate Polishing (RT-8042)
SGBD (RT-8043)
- LOT 202.41 Radiation Monitoring*
- *
What detectors are Geiger-Mueller Tube Detectors?
MSL Low Range (RT-8046 - RT-8049)
SGBD Low Range (RT-8022 - RT-8025)
Area Radiation Monitors
- LOT 202.41 Radiation Monitoring*
- *
What grid on RM-11 is for tech spec monitors?
Grid 1
Grid 6 is for EAL monitors