LOT 202.39 TSC HVAC Flashcards

1
Q
  • LOT 202.39 TSC HVAC*
    • *

What will NOT auto sequence onto the TSC DGs following a LOOP?

A

Heating Coils

  • *TSC Chillers**
  • Powered from 1W*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 202.39 TSC HVAC*
    • *

What are the TSC HVAC return fan permissives?

A
  • *At least one supply fan running**
  • Maintains TSC at positive pressure*

Other return fan off

Auto Starts if running return fan trips.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 202.39 TSC HVAC*
    • *

What will auto start the TSC HVAC supply fans?

A

Trip of Running supply fan

Interlocked to prevent both supply fans from running at once.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 202.39 TSC HVAC*
    • *

What cools the ERFDADs Computer Room AHUs?

A

TSC Chillwater

  • Humidifier supplied from potable water.
  • TSC HVAC Expansion tank makeup from Demin water. (Auto M/U)
  • Note:*
  • Computer room pressure > TSC pressure > Patm*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 202.39 TSC HVAC*
    • *

How does the TSC HVAC System respond to a high radiation?

A

Starts Makeup Fan

Secures toilet exhaust fan

High smoke in outside air will secure toilet fan but makeup fan will not start. (Recirc)

  • Note:*
  • For smoke purge, toilet fan remains running and smoke purge damper opens.
  • SI will not affect TSC HVAC