LOT 202.35 MAB HVAC Flashcards

1
Q
  • LOT 202.35 MAB HVAC*
    • *

How are the MAB supply and exhaust fans interlocked?

A

Starting Exhaust fan auto starts respective supply fan

Cannot start supply fan unless respective exhaust fan running

Normal Operation:

  • Operator takes Exhaust fan to start
  • Exhaust fan starts when exhaust damper 15% open
  • Opens Supply fan damper
  • Supply fan auto starts when supply damper 15% open

Note:
Maintains MAB at slightly negative pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 202.35 MAB HVAC*
    • *

What cools the MAB HVAC AHUs?

A

MAB Chilled Water:
Supply AHUs
MAB Locker Room, Misc Offices, and Lab Supply AHUs

CCW:
CCPs Supplementary AHUs
PDPs Supplementary AHUs

  • ECW:*
  • *CCW Supplementary AHUs**
  • ECHW:*
  • *Safety Related Supplementary AHUs**
  • TSC Chilled Water:*
  • *Counting Room Supplementary AHU**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly