LOT 202.35 MAB HVAC Flashcards
1
Q
- LOT 202.35 MAB HVAC*
- *
How are the MAB supply and exhaust fans interlocked?
A
Starting Exhaust fan auto starts respective supply fan
Cannot start supply fan unless respective exhaust fan running
Normal Operation:
- Operator takes Exhaust fan to start
- Exhaust fan starts when exhaust damper 15% open
- Opens Supply fan damper
- Supply fan auto starts when supply damper 15% open
Note:
Maintains MAB at slightly negative pressure
2
Q
- LOT 202.35 MAB HVAC*
- *
What cools the MAB HVAC AHUs?
A
MAB Chilled Water:
Supply AHUs
MAB Locker Room, Misc Offices, and Lab Supply AHUs
CCW:
CCPs Supplementary AHUs
PDPs Supplementary AHUs
- ECW:*
- *CCW Supplementary AHUs**
- ECHW:*
- *Safety Related Supplementary AHUs**
- TSC Chilled Water:*