LOT 201.16 Excore NIs Flashcards

1
Q
  • LOT 201.16 Excore NIs*
    • *

What are the primary and backup methods of determining Rx power?

A
  • Primary:*
  • *ICS (U1169)**
  • Backup:*
  • *Average 4 NIs on CP011**

Alternate:

  • ∆T
  • 1st stage pressure
  • Generator MWe
  • Condensate/Feedwater parameters
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 201.16 Excore NIs*
    • *

What will cause the following alarms?

  • PR Upper detector deviation
  • PR Lower detector deviation
  • PR Channel deviation
A
  • PR Upper Detector Deviation:*
  • *Highest PR Channel Upper Detector Current > 2% above Average detector current [60 sec TC]**

Upper detector current ≤ 50% of full power current

  • PR Lower Detector Deviation:*
  • *Highest PR Channel Lower Detector Current > 2% above Average detector current [60 sec TC]**

Lower detector current ≤ 50% of full power current

  • PR Channel Deviation:*
  • *Highest to lowest PR channels deviate > 4% [5 sec TC]**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 201.16 Excore NIs*
    • *

Where are the NIs physically located on the core?

A
  • *PR (NI-44) [45˚]**
  • 2 Detectors (Top and Bottom)*
  • *Extended Range [90˚]**
  • Center of core*
  • *PR (NI-41) [135˚]**
  • 2 Detectors (Top and Bottom)*
  • *SR (NI-31) / IR (NI-35) [180˚]**
  • SR on bottom / IR at midplane*
  • *PR (NI-43) [225˚]**
  • 2 Detectors (Top and Bottom)*
  • *Extended Range [270˚]**
  • Center of core*
  • *PR (NI-42) [315˚]**
  • 2 Detectors (Top and Bottom)*
  • *SR (NI-32) / IR (NI-36) [0˚]**
  • SR on bottom / IR at midplane*

Start at 45˚ and say PEPSI x2.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 201.16 Excore NIs*
    • *

How many detectors and channels are there for each NI?

A
  • Source Range:*
  • *2 Channels (NI-31/32)**
  • 1 detector/channel*
  • Intermediate Range:*
  • *2 Channels (NI-35/36)**
  • 1 detector/channel*
  • Power Range:*
  • *4 Channels (NI-41 - NI-44)**
  • 2 detectors/channel*
  • Extended Range NI (Gammametrics):*
  • *2 Channels (NI-45/46)**
  • 1 detector/channel And 2 Fission Chambers/Detector*

Also has channels for Visual/audio rate, Power comparator, SUR, and Flux Deviation. (1 Channel each)

  • Note:*
  • Source, Intermediate, and Power Range located on CP011.
  • Extended Range and PR are on a recorders on CP018.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 201.16 Excore NIs*
    • *

What kind of detectors are the excore NIs?

A
  • Source Range:*
  • *BF3 proportional counter**
  • Intermediate Range:*
  • *Compensated Ion Chamber**
  • Power Range:*
  • *Uncompensated Ion Chamber**
  • Extended Range:*
  • *Fission Chamber**

Accurately measures neutron leakage up to 120%.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 201.16 Excore NIs*
    • *

When removing the control power fuses and instrument power fuses, which should be removed first?

A

Instrument Power Fuses then Control Power Fuses

If control power removed first, then Rx trip or Rod control stop could occur.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 201.16 Excore NIs*
    • *

What excore NIs are available on the Remote Shutdown Panel?

A

Low Range Extended Range (NI-45A/46A)

Each extended range detector has 2 fission chambers. (1 High range / 1 Low range)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • LOT 201.16 Excore NIs*
    • *

What areas of the gas filled detector curve does each NI operate in?

A
  • Source Range:*
  • *Proportional Region**
  • Intermediate Range:*
  • *Recombination Region**
  • Inner Can*
  • *Ionization Region**
  • Outer Can*
  • Power Range:*
  • *Ionization Region**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • LOT 201.16 Excore NIs*
    • *

What are your immediate actions for a PR Flux - High Alert? (109%) [1/4]

A

Verify NIs ≤ 100%

If > 100%, Reduce power to ≤ 100% using Rods

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • LOT 201.16 Excore NIs*
    • *

Where are the SR preamps and the extended range preamps physically located?

A
  • SR Preamps:*
  • *EAB 10’ Pen Space**
  • Extended Range Preamps:*
  • *EAB 10’ and EAB 60’**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • LOT 201.16 Excore NIs*
    • *

How are the source range and intermediate range detectors compensated for gammas?

A
  • Source Range:*
  • *Neutrons and gammas interact with BF3 gas**

Neutron pulse is 10x greater than gamma pulse

  • Intermediate Range:*
  • *Outer Can lined with B-10, Inner can is not**

Outer can detects neutrons and gammas

Inner can detects gammas only

Power range doesn’t need to be compensated b/c detector has low sensitivity to gammas b/c low BF3 gas volume.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • LOT 201.16 Excore NIs*
    • *

What powers the excore NIs?

A
  • Source Range:*
  • *DP1201/DP1202**
  • Intermediate Range:*
  • *DP1201/DP1202**
  • Power Range:*
  • *DP1201 - DP1204**
  • Extended Range:*
  • *DP001/DP002**
  • Loss of power, NIs fail High.
  • If still in SR or IR, Rx will trip if DP-1201/1202 are lost.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  • LOT 201.16 Excore NIs*
    • *

When performing a NI calorimetric, what conditions must be held stable for 5 mins?

A

RTP

Feedwater Flow

Blowdown Flow

SGWL

Tave

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q
  • LOT 201.16 Excore NIs*
    • *

How would power behave if the Intermediate range was undercompensated or overcompensated?

A
  • Undercompensated:*
  • *Higher than actual reading**
  • Overcompensated:*
  • *Lower than actual reading**
  • If detectors are undercompensated, source range may not energize.
  • Slightly undercompensated is preferred.
  • Note:*
  • If compensated correctly, source range will energize ≈ 15 mins after Rx shutdown.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q
  • LOT 201.16 Excore NIs*
    • *

What are the ranges of the source, intermediate, and power range detectors?

A
  • Source Range:*
  • *100 - 106 CPS**
  • 2.5 decades of overlap*
  • Intermediate Range:*
  • *10-11 - 10-3 amps**
  • Power Range:*
  • *0% - 120%**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly