High Rise Office Flashcards
Curtain wall bearing or non bearing?
Non bearing
Churning?
Centrifugal pump is running & no water being discharged
Preferred evacuation stairs?
Fire tower; its an enclosed stairway
Between ‘38 & ‘68 fire tower is required?
True
Heavy wgt - medium - lightweight ?
20-23lbs per cubic foot, 10-20, 8-10
Fire dampers are found?
Air enters return air shaft from the plenum on each floor & whenever the air flows through fire rated partition
HVAC non-circulating mode?
- Open outside supply
- Close mixing
- Open exhaust
Auto closure of fire dampers?
Fusible link approx 50F above max temp that would normally be encountered.
Fire pumps ‘38 code; ‘68 code?
Bld over 250(‘38); 300(68)
Bypass valve is on the __ side of the fire pump?
Discharge side. It should be in closed position – stem IN. If open turn clockwise to close. You will lose 25% for 8” riser & 45% for 6” with bypass OPEN
Fire pump found?
Cellar to subcellar
Most high rise bld have two pumps side by side which are connected in __ position?
Parallel
Bld fire pumps shall be capable of delivering their rated capacity at a pressure of __ psi at the highest floor outlet?
50psi at highest floor outlet. Relief valve 15 psi above that
Strategic operating plan:
- Determine fire floor
- Verify fire floor
- Simultaneously or soon as possible begin process of ctl evacuation
- Gain ctl of bld systems hvac, elevators
- Confine/extinguish fire
1st officer establishes ICP, if he leaves before 1st Chief- who does he leave?
Preferably 1st lcc