Fission Product Barriers Flashcards
Fuel Clad Barrier LOSS
AND
Inadequate Heat Removal
> 1200F REP CETs
Fuel Clad Barrier LOSS
AND
CTMT Radiation/RCS Activity
- Containment Radiation
RU-148/149 - 2 e5 mR/hr - DE I-131 - 300 uCi/gm
Fuel Clad Barrier POTENTIAL LOSS
AND
RCS/SGT Leakage
< 21% plenum
Fuel Clad Barrier POTENTIAL LOSS
AND
Inadequate Heat Removal
- > 700F REP CETs
- < 24F subcooled
RCS Barrier LOSS
AND
Leakage
Automatic or Manual SIAS needed from RCS or SGT leakage
RCS Barrier LOSS
AND
CTMT Radiation/RCS Activity
Containment Radiation
RU-148/149 - 5 e4 mR/hr
RCS Barrier POTENTIAL LOSS
AND
Leakage
- If you need a 3rd charging pump with letdown isolated
- > 200F Subcooling with pressure rising
RCS Barrier POTENTIAL LOSS
AND
Inadequate Heat Removal
< 24F Subcooling
Containment Barrier LOSS
AND
Leakage
Ruptured SG is Faulted outside of containment
Containment Barrier LOSS
AND
Containment Integrity
- CIAS is required but not met
- Indication of leakage outside of containment
Containment Barrier POTENTIAL LOSS
AND
Inadequate Heat Removal
> 1200F REP CETs and the FRP is not working within 15 minutes
Containment Barrier POTENTIAL LOSS
AND
CTMT Radiation
RU-148/149 6 e6 mR/hr
Containment Barrier POTENTIAL LOSS
AND
CTMT Integrity
- > 60 psig
- > 4.9% H2
- > 8.5 psig with inadequate spray flow for > 15 minutes