Chapter 08: Architectural Flashcards
What areas of a data center are most vulnerable to water ingress?
Anything on or below the first floor of the building.
What is the minimum clear access height, from finished floor to any ceiling obstructions, required for a building section in a data center?
3 m (10’)
What should be the minimum slab to structure height for a data center building?
4.5 m (15’)
What are the advantages of constructing a data center in the grade kevel (ground floor) of a building?
Equipment access and floor loading considerations.
What are the disadvantages of constructing a data center on the upper floors of a building?
- Equipment access
- Floor loading considerations
- Structural instability in areas with major lateral force issues (hurricane, wind seismic)
What equipment shall be in the command center?
A command center shall house environment monitoring equipment and computer systems monitors.
What is the size and weight of the equipment for which the computer/ telecommunications equipment delivery pathway, including doors, shall be designed?
Delivery pathways shall be designed for equipment as large as 3 m (10’) long by 1.2 m (4’) deep by 2.4 m (8’) high, weighing greater than 3400 kg (7500 lbs)
What is the typical time frame for a data center to significantly change its ITE inventory?
3 to 5 years
What is the maximum opening size for a glazed opening in a computer room door
Glazing within doors shall not exceed 0.065m^2 (100”^2).
What shall be the minimum thickness for data center doors?
45 mm (1.75 in)
What is the minimum access floor height required above the slab?
450 mm (18”)
What is the minimum clearance that shall be maintained from the sprinklers to raceways, cabinets, and racks to ensure they do not disrupt the sprinkler distribution pattern subject to the AHJ?
450 mm (18”)
What should the minimum access floor height above the slab for computer rooms with higher power density equipment where the underfloor space is used for cooling?
900 mm (36”)
What is the minimum recommended ceiling height for computer room spaces (from slab-to-slab)?
4.5 m (15’ or greater)
What is the minimum ceiling height from the finished floor to any obstruction in data center computer rooms and telecommunication spaces?
3 m (10’)