Brown Bauhaus RA 9514 Part 2 Flashcards

1
Q

The required slope of all horizontal runs of dry standpipes systems for the purpose of draining

A

20%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

All 102 mm dry standpipes shall be equipped with what type of service connection?

A

Four-way fire service connection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The required minimum height of raised letters of “DRY STANDPIPE” plate signs permanently attached to all fire service street connections

A

25 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Wet standpipes shall be located so that all portions of the buildings are within what distance from the nozzle attached to 22 meters of the hose?

A

6 meters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The required minimum number of means of egress from any balcony, mezzanine, storey, or portion thereof of buildings

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The required size of standpipes

A

64 mm (2 1/2”) in diameter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The required minimum size of hoses that supply each wet standpipe outlet

A

38 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The required size of a combination standpipe system

A

150 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The required minimum size of sleeves of basement pipe inlet’s inside diameter extending through the floor and terminating flush with or through the basement or cellar ceiling and shall have a top flange recessed with an inside shoulder to receive the lid

A

200 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The required travel distance for portable fire extinguishers

A

10 meters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Portable fire extinguishers shall not be installed as the sole protection for flammable liquid hazard of appreciable depth where the surface area exceeds how much area?

A

1 sqm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

An exterior way of exit access shall be arranged so that there are no dead-ends in excess of how much in length?

A

6 meters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fire extinguishers for the protection of delicate electronic equipment shall be selected from what type of chemicals?

A

Either carbon dioxide type or halogenated agent type

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The required minimum protection rating of doors in required smoke partitions

A

20 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is required to be provided where ducting of air-conditioning and ventilating system passes through from one room to another room or from one fire barrier to another fire barrier?

A

Automatic fire dampers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Doors required to be of the side-hinged or pivoted- swinging type shall swing in the direction of egress travel where serving a room or area with an occupant load of how many persons?

A

50 or more

17
Q

A door shall swing in the direction of egress travel when used in an exit enclosure or where serving a high hazard contents area unless it is a door from an individual living unit that opens directly into an exit enclosure. During its swing, any door in a means of egress shall leave how much of the required width of an aisle, corridor, passageway, or landing?

A

Not less than one-half of the width

18
Q

Doors on buildings on four (4) or more storeys in height shall be provided with what device to provide access out of the stairway to another exit?

A

Re-entry mechanism

19
Q

Re-entry mechanism in doors shall be provided in what floor intervals which the said floors provide a way out of the stairway?

A

Every 4 floors

20
Q

The maximum width of single doors in doorways

A

122 cm

21
Q

The required minimum fire-resistance rating of a separation that protects an exit from other parts of the building and when the exit connects three (3) storeys or less, regardless of whether the storeys are connected are above or below the story at which the exit discharge begins?

A

1 hour

22
Q

The required minimum width of any exit access corridor serving 50 or more persons

A

112 cm

23
Q

The required minimum width of door openings in means of egress

A

71 cm

24
Q

The required maximum height between landings for new stair construction

A

3.66 meters

25
Q

The maximum number of rows of seats that open onto an aisle at one side only

A

7 seats

26
Q

The required minimum width of aisles when serving 60 seats or less

A

76 cm

27
Q

The required maximum distance of the length of travel to an exit door by any aisle

A

46 m

28
Q

The required minimum height of railings above the floors of the fasciae of boxes, balconies, and galleries

A

66 cm

29
Q

The number of revolving doors used as exit doors is required not to exceed the number of swinging doors used as exit doors within how many distances?

A

6 meters

30
Q

The required maximum travel distance to an exit from any point in any building protected throughout by an approved, supervised automatic sprinkler system

A

61 m