The required slope of all horizontal runs of dry standpipes systems for the purpose of draining
20%
All 102 mm dry standpipes shall be equipped with what type of service connection?
Four-way fire service connection
The required minimum height of raised letters of “DRY STANDPIPE” plate signs permanently attached to all fire service street connections
25 mm
Wet standpipes shall be located so that all portions of the buildings are within what distance from the nozzle attached to 22 meters of the hose?
6 meters
The required minimum number of means of egress from any balcony, mezzanine, storey, or portion thereof of buildings
2
The required size of standpipes
64 mm (2 1/2”) in diameter
The required minimum size of hoses that supply each wet standpipe outlet
38 mm
The required size of a combination standpipe system
150 mm
The required minimum size of sleeves of basement pipe inlet’s inside diameter extending through the floor and terminating flush with or through the basement or cellar ceiling and shall have a top flange recessed with an inside shoulder to receive the lid
200 mm
The required travel distance for portable fire extinguishers
10 meters
Portable fire extinguishers shall not be installed as the sole protection for flammable liquid hazard of appreciable depth where the surface area exceeds how much area?
1 sqm
An exterior way of exit access shall be arranged so that there are no dead-ends in excess of how much in length?
6 meters
Fire extinguishers for the protection of delicate electronic equipment shall be selected from what type of chemicals?
Either carbon dioxide type or halogenated agent type
The required minimum protection rating of doors in required smoke partitions
20 minutes
What is required to be provided where ducting of air-conditioning and ventilating system passes through from one room to another room or from one fire barrier to another fire barrier?
Automatic fire dampers