WET VENTING AND CIRCUIT VENTING CODE Flashcards
1
Q
- 5.3.1
2) fixtures with fixture outlet pipes less than ___ inches in size shall be separately vented or separately circuit vented
A
2”
2
Q
- 5.3.1
4) A soil or waste pipe having a hydraulic load not greater than ___ fixture units is permitted to act as a relief vent for a branch that is circuit vented
A
6 FU
3
Q
- 5.3.1
4) A soil or waste pipe having a hydraulic load not greater than 6 fixture units is permitted to act as a _____ vent for a branch that is circuit vented
A
relief
4
Q
- 5.3.1
5) A symmetrically connected relief vent is permitted to serve as a combined relief vent for a maximum of __ branches that are circuit vented, provided they are not more than 8 circuit vented fixtures connected between the combined relief vent and each circuit vent
A
2
5
Q
- 5.3.1
5) A symmetrically connected relief vent is permitted to serve as a combined relief vent for a maximum of 2 branches that are circuit vented, provided they are not more than ___ circuit vented fixtures connected between the combined relief vent and each circuit vent
A
8
6
Q
- 5.3.1.
6) additional circuit vents shall be required:
A) where each cumulative horizontal change in direction of a branch served by a circuit vent exceeds __° between vent pipe connections, or
b) we are more than 8 circuit vented fixtures are connected to a branch between vent pipe connections
A
45
7
Q
- 5.3.1.
6) additional circuit vents shall be required:
A) where each cumulative horizontal change in direction of a branch served by a circuit vent exceeds 45° between vent pipe connections, or
b) where are more than __ circuit vented fixtures are connected to a branch between vent pipe connections
A
8
8
Q
- 5.3.1
7) A soil or waste pipe is permitted to serve as an additional circuit vent in accordance with sentence 6, provided the soil or waste pipe is sized as a wet vent in conformance with article 2.5.8.1 and is not less than ____ inches in size
A
2”
9
Q
- 5.3.1.
9) A circuit vented branch including the fixture drain downstream of the circuit vent connection, shall be sized in accordance with article 2.4.10.7, except that it shall be not less than
a) _ inches, where traps less than _ inches in size are circuit vented, or
b) 3 inches, where traps 2 inches in size or larger our circuit vented
A
2
2
10
Q
- 5.3.1.
9) A circuit vented branch including the fixture drain downstream of the circuit vent connection, shall be sized in accordance with article 2.4.10.7, except that it shall be not less than
a) 2 inches, where traps less than 2 inches in size are circuit vented, or
b) _ inches, where traps _ inches in size or larger are circuit vented
A
3
2
11
Q
- 5.3.1
1) A soil-or-waste pipe is permitted to serve as a wet vent, provided
b) the number of wet vented water closets does not exceed __
A
2
12
Q
- 5.3.1
1) A soil-or-waste pipe is permitted to serve as a wet vent, provided
c) where __ water closets are installed, they are connected at the same level by means of a double sanitary T fitting if the vent pipe is vertical and by means of a double Y fitting if the vent pipe is horizontal
A
2
13
Q
- 5.3.1
1) A soil-or-waste pipe is permitted to serve as a wet vent, provided
c) where 2 water closets are installed, they are connected at the same level by means of a double sanitary __ fitting if the vent pipe is vertical and by means of a double Y fitting if the vent pipe is horizontal
A
T
14
Q
- 5.3.1
1) A soil-or-waste pipe is permitted to serve as a wet vent, provided
c) where 2 water closets are installed, they are connected at the same level by means of a double sanitary T fitting if the vent pipe is vertical and by means of a double __ fitting if the vent pipe is horizontal
A
Y
15
Q
- 5.3.1
1) A soil-or-waste pipe is permitted to serve as a wet vent, provided
d) the water closets are installed _________ of all other fixtures
A
downstream