Hydronic Heating COPY Flashcards
What are the four main hydronic heating piping layouts that are commonly installed?
1)One pipe - series loop. AKA A perimeter heating system. 2) One pipe - monoflow or diversion tee. 3) Two pipe - Direct return. 4)Two pipe - Reverse return.
What’s the purpose of an expansion tank in a hot water heating system and where should it be located?
It prevents the pressure relief valve from going off when the boiler fires up - in the end it prevents more water from getting into the system and causing corrosion. The expansion tank should be located upstream from the system pump. The place where the expansion tank is attached is commonly known as the point of no pressure change.
Where’s the best location for the circulator to be installed on a hydronic heating system?
Downstream of the expansion tank. Another possible location would be on the return piping into the boiler. In some cases a circulator can be placed on both the supply and the return piping. This would be more likely in a situation that requires a constant and steady flow, such as a radiant floor heating system.
What’s the pressure relief valve in a residential boiler usually set to?
30 psig.
Where is the pressure relief valve usually located?
On the boiler.
How much should a pressure relief valve be able to relieve?
100% of the rating of the boiler.
What would cause a pressure relief valve to start dripping?
A waterlogged expansion tank.
What is make-up water on a hydronic heating system?
Make up water is water that’s introduced into the closed hydronic system when water either leaks out through a break in the system or more commonly when the relief valve kicks off.
What’s another name for a pressure reducing valve that reduces the pressure before it gets into the system?
The pressure reducing valve is also known as the feed water valve.
What’s the pressure in a hydronic heating system usually set to?
12-20 psig.
What is a flow check valve and where’s it located?
A flow check valve is a valve that prevents the unwanted flow of water through a system when the burner isn’t on. It’s located on the supply leaving a boiler.
What’s the difference between a flow check valve and a flow switch?
A flow switch ensures flow through the system before the burner will kick on.
Where would you install the backflow preventer in a boiler system?
A backflow preventer’s installed in the make-up water line on the boiler.
What’s the typical backflow preventer installed in a residential boiler?
The Watts 9D.
Where would the PRV be installed in relation to the boiler?
The PRV’s installed on the make-up water line.
What’s the PRV set at in a typical residential application?
Between 12-20 psig.
What’s an air scoop? Where’s it located?
An air scoop is a water / air seperator. It’s attached to the expansion tank which will be located upstream of the system pump. This would be where the temperatures highest and the pressure’s the lowest in the system.
What is the “R” value of a material? What’s the “U” value of a material? What’s the DTD (Design Temperature Difference refer to when calculating heat loss from a building?
“R” value = #Hours / BTU / Degrees F / ft2
“U” Value = #BTU’s / Hour / Degrees F / ft2
“U” Value = 1 / R Value.
DTD = IDT - ODT.
Note: IDT means inside diameter temperature. ODT means outside diameter temperature. The DTD is the difference in temperature from the inside of the building in relation to the outside of the building during the coldest times of the year. This difference in temperature is used to calculate heat loss.
How would you calculate the flow rate required in a hydronic heating system?
GPM (Gallons Per Minute) = BTUH / (Change in temp. x 500).
Note: The normal temp. drop across a system is 20 Degrees F, but for infloor systems its 10 Degrees F.
What’s a “fire tube,” and what’s a “water tube” in relation to boilers?
A fire tube is where hot gases from a fire run through tubes that are surrounded by water. A water tube is filled with water and heated externally by fire.
What’s a conventional boiler? Is it more or less efficient than a condesing boiler?
A conventional boiler is one that’s products of combustion remain relatively hot and do not condense. They’re vented through the flue. Not as efficient as a condensing boiler.
What’s a condensing boiler? Is it more or less efficient than a conventional boiler?
A condensing boiler is one in which most of the heat is removed and reused from the products of combustion. and the products of combustion cool down enough to condense. It’s more efficient than a conventional boiler.
What extra component would you require if you used boiler water to heat domestic hot water?
A heat exchanger (an indirect connection.)
What’s the difference between a gravity hot water heating system and a closed loop hydronic system containing a circulator?
Gravity System: Larger pipe, no pump, may be open at top (no circulator.
Closed loop hydronic system: Smaller pipe, pump, pressurized.