TS 3.1.2 SDM - RX Trip Breakers Closed Flashcards

1
Q

Reactivity shall be controlled by what 3 things?

A

a. SDM shall be > COLR value
b. K(N-1) shall be <0.99 when Tc < 500F
c. RX Criticality shall not be achieved with shutdown group CEA movement

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

MODES of applicability?

A

Modes 3, 4 and 5 with RX Trip Breakers CLOSED and CEA drive system capable of CEA withdrawal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

SDM not in Limits?

A

CONDITION A: Borate in 15 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

K(N-1) not in Limit OR RX criticality by Shutdown group?

A

Vary CEA’s AND Borate (both in 15 minutes)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly