Tech Specs (class room) Flashcards
1
Q
Mode 1
A
- Power Operation
- RTP >5%
2
Q
Mode 2
A
- S/U
- <=5%
3
Q
Mode 3
A
- Hot Standby
- > =350 degrees
4
Q
Mode 4
A
- Hot Shutdown
- 349-201 degrees
5
Q
Mode 5
A
- Cold Shutdown
- <=200 degrees
6
Q
Mode 6
A
Refuel
7
Q
LCO 3.0.1
A
LCOs must be met
8
Q
LCO 3.0.2
A
Eneter conditions if LCO is not met
9
Q
LCO 3.0.3
A
Shutdown if there is not an LCO for condition. Mode 3 in 7 hours, Mode 4 in 13 hours and Mode 5 in 37 hours
10
Q
LCO 3.0.4
A
Mode changes with LCO active can happen when:
A- Allows me to be in condition forever
B- Risk assesment made
C- LCO has note allowing condtions
11
Q
LCO 3.0.4 exceptions?
A
- LTOP system shall be operable
- One ECCS train shall be operable
- 4 AFW flow paths and 3 AFW pumps shall be operable
- AC sources (2 qualified circuits for offsite, 2 EDGs)
12
Q
SL 2.1?
A
- Reactor Core SL. (DNBR ratio, and peak fuel centerline temperature)
- RCS pressure In modes 1-5 shall be less than 2735psig
13
Q
SL 2.2 SL Violations
A
- If 2.1 is violated, restore compliance and be in mode 3 within 1 hour
- If 2.2 is violated in mode 1 or 2 then restore compliance and be in mode 3 within 1 hour, if in Mode 3-4-5 restore compliance within 5 minutes.