CVCS (Class room) Flashcards
1% in the PZR is equal to how many gallons?
50.56 gallons per percent
1 inch in the VCT is equal to how many gallons?
23.99 gallons
VCT levels from LT-112
30-39” Normal divert for LCV-115A
16.6” For Auto swap recovery.
12.4” For Auto swap LCV-115C/B
Need both LT-112 and LT-115 for swap
VCT levels for LT-115
51.6” Full divert for LCV-115A
48.6” High alarm
45.6” LCV-115A back to VCT
24.4” Auto makeup stops
20.2” Auto makeup starts
16.6” Swap recovery
12.4” Swap
Both LT needed for Swap
Tavg, Power, PZR level
corralation
Power- 0%-100%
Tavg-547-575.9 degrees
PZR lvl 22.2-53.3%
What is the ratio needed for letdown to charging through the Regen heat exchanger
2:1
Letdown:charging
Primary water pumps
MCC-1/2
20 starts with 2 minutes
Boric Acid Pumps
Mcc-5/6
13 starts with 3 mins
Charging pumps
DS/E1/E2
4 starts with 5 mins
Phase A valves in CVCS
CVC-200A/B/C Letdown Orifice Isolation Valves
LCV-204A/B Letdown Line Isolation valves
CC-739 CCW to Seal Water Return Hx
Phase B valves in CVCS
CVC-381 Seal Water Return Isolation Valve
All 3 way valves in CVCS do what?
Fail to VCT
All Letdown Valves fail Close except?
TCV-144 Non-regen HX temperature control valve
PCV-145 Low Pressure Letdown Valve
All charging Valves fail Open except?
CVC-311 Aux PZR spray
CVC-307 Seal bypass
Boric acid and makeup valves fail closed except
FCV-113A Boric Acid to Blender