PZR pressure tree Flashcards
PZR tree
2235
Spray valves full closed
(NOP)
PZR tree
2250 (+15)
Proportional Heaters Full off
PZR tree
2260 (+25)
Spray valves start to open
PZR tree
2285 (+50)
When coming down in pressure spray valves start to close
PZR tree
2310 (+75)
Spray valves Full open (High pressure alarm)
PZR Tree
2335 (+100)
PORV open
PZR tree
2376
Reactor Trip
PZR tree
2485
Safety Valves open
PZR tree
2735
Safety Limit
PZR tree
2220 (-15)
Proportional heaters fully on
Back up heaters turn off
PZR tree
2210 (-25)
Backup Heaters come on
PZR tree
2185 (-50)
Low Pressure Alarm
PZR tree
2000
SI Block Premissive
Power Operated Reliefs close
PZR tree
1844
Reactor Trip
PZR tree
1715
Safety injection
whats the difference between the PORV setpoints?
2335 opens PCV-456
2340 opens PCV-455C