SI signals Flashcards
SI signal
Low PZR pressure
coincident, setpoint
2/3 @ 1715psig
Si signal
Hi Steam Line D/P
coincident, setpiont
2/3 detectors on 1/3 lines @ 100psid
Si signal
Hi CV Pressure
coincident, Setpoint
2/3 @ 4psig
SI signal
Hi Hi CV pressure
coincident, setpoint
2/3 detectors on 2/2 groups @ 10psig
SI signal
Hi Steam Line flow
Coincident, setpoint,and what else is needed?
Setpoint is linear, 37.25% to 109% flow from 20-100% power. (1/2 detectors on 2/3 lines)
AND
Low Tavg <543°F on 2/3 loops or
Low steam line pressure of 614psig 2/3 S/Gs
SI signals
Manual
1/2 pushbuttons
What SI signal does 2000psig block
Hi steam line DP and PZR low pressure
What SI signals does the Tavg block at what temperature?
High steam line flow and Hi-Hi CV pressure when Tavg >543 (2/3 loops)
At low power what part of the High Steam line flow signal are we closer too?
At 0% power we are closer to Tavg of 543
At high power what part of the high steam line flow signal are we closer too?
At 100% we are closer to Steam line pressure of 614psig.
0%-1000psig
100%-800psig
SI signal causes what?
SPAREFCCC
- Safeguard sequence actuation
- Phase A and IVSW
- AFW
- Reactor Trip
- EDGs
- Feedwater Isolation
- Cv ventilation Isolation
- Control Room Pressurization
- CLose normal dampers
How long before SI signal can be reset? what lets you know?
2 minutes, white light above EDGs
Auto Spray will do what?
Phase B
Spray
SI actuation
Steam line Isolation
Man. spray will do what?
Spray
Phase B
CV ventilation isolation
SI valves that move:
RHR-744A/B (RHR Hx Outlet)
SI-870A/B (Bit Outlet)