sequencer Flashcards

1
Q

Sequencer

What turns on after 5 seconds?

A

A/B/C SI pump starts
(B only if racked in)

SI only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Sequencer

What turns on after 15 seconds?

A

A/B RHR pumps start

SI only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Sequencer

What turns on after 20 seconds?

A

A/C SW pumps start
(Signal to start both SWBPs. SI auto start, SBO waits until 30psig in SW header)

Both SI and SBO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Sequencer

What tuns on after 25 seconds?

A

B/D SW pumps start
(Signal to start both SWBPs. SI auto start, SBO waits until 30psig in SW header)

Both SI and SBO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Sequencer

What turns on after 30 seconds?

A

1/3 HVH units start on SI

CCW pump B/C start on SBO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Sequencer

What turns on after 35 seconds?

A

2/4 HVH units start

SI only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Sequencer

39.5 seconds?

A

A/B AFW starts

Both SI and SBO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

List the SI sequencer

A

5 sec- A/B/C SI pumps
15 sec- A/B RHR pumps
20 sec- A/C SW pumps (SWBPs)
25 sec- B/D SW pumps (SWBPs)
30 sec- 1/3 HVH units
35 sec- 2/4 HVH units
39.5 sec- A/B AFW pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

List the SBO sequencer

A

20 sec- A/C SW pumps (SWBPs with 30psig)
25 sec- B/D SW pumps (SWBPs with 30psig)
30 sec- B/C CCW pumps
39.5 sec- A/B AFW pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens if a safety injection singal comes in while a blackout sequence is in progress?

A
  1. If the EDG output breaker is closed, the SI squence will start and the SBO signal is blocked and stops.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Which sequencer sheds loads?

A

Blackout

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What loads are not shed on a blackout?

A

MCC-5/16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What turns off a CCW pump?

A

Having 3 signals, UV, SI, and Spray

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What turns off charging pump?

A

UV and SI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

SI Sequencer must have what to start?

A

Power on respective bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Blackout sequencer starts

A

When power on the bus is gone

17
Q

When will A CCW pump start if it was not already running?

A

Low pressure if power is availble on DS bus