Tech Specs Flashcards

1
Q

3.1.3 CONTROL ROD OPERABILITY

A
Modes 1 &2
1 W/D ROD STUCK
--DISARM IN 2 HRS
--CRD EX IN 24 HRS
--SDM IN 72 HRS
2+ W/D RODS STUCK	
--DISARM in 2 HRS  & MODE 3 IN 12
1+ CR INOP FOR other REASONS	
--FULLY INSERT in 3 HRS & DISARM in 4 HRS
2+ INOP CR not in Comp with BPWS	
--Restore to OPER in 4HRS Or Restore Comp with BPWS in 4 hrs
9+ CR INOP	
--Mode 3 in 12 HRS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

3.4.1 2 Recirc Loops w/match flows or SINGLE w/Limits applied

A

Modes 1 & 2
NOT MET Satisfy in 24 HRS
Time Limit or NO RECIRC Mode 3 in 12 HRS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

3.4.5 RCS LKG Detection

A
Modes 1,2, & 3
DWFD Mon INOP	Restore in 30 days
FPM Part/Gas both  INOP	Grab Samples Once/12 hrs &
Restore in 30 Days
ALL INOP	3.0.3 Immediately
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

3.4.7 SDC-Hot Shutdown-2 Loops Operable and 1 in operation if No Recirc

A

Mode 3 < 138 psig
1+ SDC Loops INOP Restore Immed &
Ver Alt DHR for each INOP in 1 hr
AND Mode 4 in 24 hrs
NO SDC or RECIRC in operation Restore 1 sys Immed &
Verify Alt Circ in 1 hr & Once/12 & Mon Rx Cool temp/press hrly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

3.5.1 ECCS and ADS

A
Modes 1 & 2/3 >150 for HPCI/ADS
1 LOW PRESS
-- 7 days
HPCI
-- RCIC 1 HR & 14 days
HPC1/1 LO PRESS
--restore 72 hours
2+ ADS
-- 12 / 36
2+ LO PRESS
-- 3.0.3
HPCI/2 ADS
-- 3.0.3
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

3.6.1.3 Each PCIV except rx/torus

Vac Brkr Operable

A
Modes1,2 &3 when inst req’d to be operable
1+ Pen w/1 PCIV INOP
--ISOL 4 hr/8 hr MSL/ Ver  31 days
1+ Pen w/2 INOP
--ISOL in 1 hour
1+ Pen w 1 INOP if ONLY 1
--ISOL in 4 hr (EFCV 12 hr) Ver 31d
1+ Pen w/lkg unaccept
--Restore 4 hr
Otherwise
--3 in 12/4 in 36
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

3.6.1.3 Each PCIV except rx/torus
Vac Brkr Operable
Mode 4 & 5

A

Req’d PCIV INOP
–Suspend OPDRV’S OR
Return SDC PCIV’s to Operable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

3.7.2 PSW

A
1,2,3
1 PUMP or 1 TB ISOL
-- 30 days
1 PUMP IN EACH LOOP
-- 7 days
1 TB ISOL in EACH LOOP
-- 72 hrs
1 SUBSYSTEM INOP
-- 72 hrs
BOTH SUBSYS OR UHS
-- 3 in 12 / 4 in 36
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

3.8.1 AC SOURCES OP

A

Modes 1,2, 3
1 OFFSITE CKT Brkr Align 1/8 HRS and
Dec Feat w/no offsite INOP in 24
And Restore 72 hrs/17 days
1 same unit or swing DG Brkr Align 1/8 HRS and
Dec Supp Feat INOP if Red in 4
Surv or Comm Cause in 24 hrs
Restore 72 hrs/14 days/17 days
1 opposite Unit DG Brkr Align 1/8 HRS and
Dec Feat w/no offsite INOP in 4
Surv or Comm Cause in 24 hrs
Restore 7days/14 days
2+ Offsite CKT Dec Feat w/no offsite INOP in 12
AND Restore All but 1 /24 hrs
1 offsite ckt and 1 Req’d DG Restore Either in 12 hours
2+ SameU or Swing DG Restore All but 1 in 2 hrs
No DG capable U2 LPCI lc Restore 1 in 2 hrs
1+ Offsite and 2+ DG or
2+ Offsite and 1 DG 3.0.3 Immed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

3.8.7 Dist Sys OPER

A
Modes 1, 2,3 
1+ Opp Unit AC or DC	Restore 7 days
1+ Same U/Swing DG DC	Restore 12 hrs/16 hrs 3.8.7.a
1+ Listed Bus	8 hours
1 Sta Svc DC	2 hours
2+ Subsys that cause LOF	3.0.3 Immed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

3.9.1 R/F Interlocks

A

Modes: Invessel Fuel Moves
1+ Intlk INOP Suspend Immed OR
Insert ROD BLOCK and All Rods IN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

3.9.2 R/F 1 Rod Out Interlock

A

Modes: 5/Mode Sw in RF/any Rod out

R/F 1 rod out intlk INOP Suspend CR w/d and ALL Insertable Rods IN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

3.9.3 CR Position

A

Mdoes: Loading Fuel into vessel

1+ CR Withdrawn Suspend Fuel Load Immed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

3.9.4 C/R Full IN POS

A
Mode 5
1+ W/D CR INOP	
--Suspend Invessel Fuel
--Suspend CR W/D
--Insert Rods in cells w/fuel
OR
Insert CR w/INOP FI ind
AND Disarm Immed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

3.9.5 Each WD CR Operable

A

Mode 5

1+ WD CR Inop INSERT Immediately

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

3.9.6 RPV Water Level >/= 23’ above Irrad Fuel

A

Fuel/CR handling in RPV
RPV H2O Lvl not in lmt

Suspend Movement/CR Handling Immediately
17
Q

3.9.7 SDC Hi RWL >/= 22’ 1/8”

1 SDC subsys OPER and IN SERVICE

A

5 w/22’1/8” above flange

Req’d SDC Subsys INOP

Verify ALT means of DHR in 1HR/Once PER 24 HRS

NO SDC IN SVC VER ALT CIRC W/in 1 HR and ONCE/12 HRS and mon Cool temp hrly

18
Q

3.9.8 SDC LO RWL =22’1/8”

2 SDC subsys OP W/1 IN svc

A

5 <22’1/8”
Above flange

1 OR 2 Subsys INOP Verify ALT means of DHR in 1HR/Once PER 12 HRS
NO SDC IN SVC VER ALT CIRC W/in 1 HR and ONCE/12 HRS and mon Cool temp hrly