How do CHA-UV-505 and 506 FAIL?
Fail CLOSED on Loss of Air or Power
U1 has a LOOP. PKA-M41 has just failed as well. What is status of CBO?
It is re-established with loss of M41
What is the purpose of DFWCS “RTO”?
Prevent a post-trip overcooling transient
Without Spray Pond support, how long can the EDG’s run?
2.6 Minutes Loaded
15 Minutes Unloaded
On a loss of 2 PN busses, what would we expect without Operator action?
RX TRIP and Full ESFAS Actuation
On a SIAS and a LOP, what happens to NNN-D11/12/15/16?
D11 and 12 = Transfer to Class MCC’s
D15 = De-energized
D16 (U1/2) = De-Energized
D16(U3) = Transfer to Class MCC
When do PZR safeties relieve?
2475 PSIA
On a loss of IAA-UV-2 what is impact to CVCS?
515 and 516 close
- UV-2 closes on CSAS “A” and Loss of PKA
What are the flow rates for SI PUMPS for a 1 Hour MIN FLOW LIMIT and UNLIMITED run times?
CS = 150 GPM (1 Hour) / 2100 GPM (UNL) LPSI = 100 GPM (1 Hour)/ 2400 GRPM (UNL) HPSI = 85 GPM (1 Hour)/ 225 GPM (UNL)
What do we classify Primary to Secondary Leakage as?
IDENTIFIED LEAKAGE
As PZR LVL lowers, what type of actions would be taken to STOP the lowering (if can’t stop lowering)?
- Start ALL available CH Pumps
- Isolate LD
- Trip RX
What alarms would we expect if Letdown was to ISOLATE (Time Critical Action-10 Minutes)?
- HI REGEN OUTLET TEMP
- LD LOW PRESSURE
- LD RAD MONITOR LOW FLOW
What are the ways that CHN-UV-231P (Seal Injection Isolation valve) FAILS?
- Fails Open on Loss of Air/Power
2. Closes on HI-HI (150F) or LO-LO (70F), take open to reset (Temp inst. fails = doesn’t close)
The RVLMS normally has a delta of 90F, what would indicate a VOID?
Delta of 200F or HJTC > 700F
How is Turbine Cooling Water temperature maintained during Normal Ops?
Adjusting HX Outlet valve and Bypass valve