Secondary Chem Control (SC) Flashcards

1
Q

What pressure is the BFT maintained at by the pressure regulating valves 4A and 4B?

in what order do they open?

A

200 psig

4A first to the HDT equalizing line
4B opens to the CD if 4A is full open and can’t maintain pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What cools the B/D heat exchanger?

Where is flow returned to?

A

CD pump discharge

MFWP suctions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How do the S/G B/D isolation valves fail on a loss of air or power?

A

closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What will automatically close the S/G blowdown containment isolation valves?

A

SAM

SIAS
AFAS
MSIS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What will automatically close the S/G blowdown SAMPLE containment isolation valves?

A

SAM

SIAS
AFAS
MSIS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where can the S/G blowdown liquid be discharged to?

When would flow isolate automatically?

A

3 LPFWHs

to the B/D demins
retention tanks

hi temp coming out of the B/DHX

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which S/G B/D valves auto close on a B/DHX high temp signal?

A

3B (through B/D demins) and 3C (to retention tanks)

NOT 3A (to LPFWHs)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens if there is a hi temp signal coming out of the B/DHX and the BYP DEMIN MODE LV 3A position is not selected at the handswitch?

A

BFT will overfill due to no discharge flow path

BFT reliefs will eventually open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is the B/D Demins discharge directed to?

A

the condenser

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What cools the B/D demin sample coolers?

A

WC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What cools the B/D demin field coolers?

A

NC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What radiation monitors are associated with S/G Blowdown?

A

RU-4/5
detects radioactivity downstream of the sample coolers to detect primary to secondary leaks

RU-200
isolates flow (V-1283) to the retention tanks if radiation detected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How are S/G blowdown constants verified and entered?

A

updated in the PC and CMC

documented IV on new B/D constants before numbers are typed into the computer

documented CV when entering constants into the computer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which S/G blowdown valves fail closed on a loss of instrument air?

What is the exception?

A

All fail closed except for the BFT pressure control valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What valves are affected in the S/G blowdown system on a CSAS?

How do we get them back?

A

INSIDE containment isolation valves (500 series) fail closed
CSAS isolates IA to containment, 500 valves fail closed on loss of air

take inside containment isol valves HS to close, override and open IA to containment valve, clear downstream side of valve of voids before reopening in a controlled manner to prevent damage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is required prior to initiating S/G blowdown?

A

condenser vacuum
CD demins inservice
chemistry notified

17
Q

How many S/Gs can be in High-Rate blowdown to the Condenser?

A

1 at a time

18
Q

What is the purpose of the wet layup pumps?

A

clean/remove chemicals and suspended solids during extended shutdowns

maintain chemistry requirements during shutdown when in recirculation

19
Q

How do the S/G blowdown rate line valves fails on a loss of air or power?

A

fail closed

20
Q

When on High-rate S/G blowdown, how many valves are open?

A

2

high rate and abnormal rate valves

21
Q

What is the purpose of Polyacrlic acid (PAA)?

where is it injected?

how is it operated?

A

promotes suspension of particulates
inhibits the ability of iron oxide particles to clump together
inhibits the ability of iron oxide to stick to surfaces

upstream of the FW venturi flowmeters and corrosion product monitors

locally by AOs on 100’ TB