Diesel Generator/Diesel Fuel Oil (DG) Flashcards
How long does it take a DG to start and attain full-load speed and accept load on a cold start?
10 seconds
What is the rated output of the DG?
5500 KW continuous and 6050 KW for 2 of 24 hours
What signals automatically start the diesel generator?
SIAS
AFAS
LOP
CSAS (test mode unless SIAS also present)
WHat is rated speed and voltage of the DGs?
600 rpm
60 hz
4160 VAC
Why should operation of the DG above 4300 VAC be minimized?
prevent over voltage on downstream MCCs
Operating the Diesel Generator in parallel with offsite power, while picking up reactive load (+VARS), may cause increased voltage conditions PBA-S03/ PBB-S04.
What is the lower limit for operating load on the DGs?
25%
When the DG mode control switch is in ‘OFF’, what does that mean for operability?
inoperable
What are the DG emergency Trips?
Overspeed 660 RPM (ONLY Mechanical overspeed trip)
Generator Differential (current going in is different then what’s going out)
Low Lube Oil pressure (30 psig on 2/4)
How can the DG be stopped mechanically?
Butterfly Valve
Manuel Rack
○ Pull and HOLD
DG Fuel Oil Day Tank outlet valve
How long can the DG run without the SP pump running?
15 minutes unloaded
2.6 minutes loaded
What provides power to the ‘A’ DG control panel, control circuits and indication?
‘B’ DG?
NKN-D42
NKN-D43
On a loss of NK to the DG, what is affected?
What is still available?
Will the DG trip if running?
normal test run functions and control room indications
ability to emergency start/run the diesel (cant start from the control room)
No
What does Pk power for the DGs?
What happens to the DGs on a loss of PK?
Why is a loss of PK so detrimental if the DG is running and supplying power to the bus?
control circuits and provides field flashing power
loss of controls, starting circuit and electrical protection
If DG is running, DG trips and Output breaker fails as is
if paralleled to offsite power, DG will motorize
At what RPM does the DG trip on overspeed?
660 RPM (110%)
What does the overspeed governor isolate at the trip setpoint?
isolates fuel and combustion air
What is the only mechanical automatic trip available for tripping the DG on a loss of Control Air?
overspeed trip
What is the purpose of the Turbocharger on the DGs?
increase engine efficiency and fuel economy
How would the turning gear disable the DG from starting?
Two pneumatic Turning Gear Interlocks prevent cranking air from starting the engine when the turning gear is not fully disengaged
How much fuel does the DG use at full rated load?
6.55 gpm
What is the tech spec minimum level for the DG Fuel Oil Storage Tank?
How many days of run time does this give us?
> /= 80% (~71,383 gal)
7 days of continuous use at 100% rated output
Where are the DG Fuel Oil Transfer pumps powered from?
PH
What is the minimum Tech Spec level for the DG fuel Oil Day Tank?
What is the basis for this?
2.75’ (550 gal)
60 minute supply with 10% margin if DG is at full rated power
What are the makeup sources for DG jacket water?
Normal - DW
backup - CT
emergency - FP
What does DG jacket water supply cooling water to?
When does the DG become inoperable on JW temperature?
engine cylinder jackets
main governor
turbo
<105*F