Control Room Tell tale signs of loss of power Flashcards

1
Q

How can you tell if NNN-D11 was lost?

A

Alarm window on board 1
RCP seal injection controllers (left 2 go dark)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How can you tell if NNN-D12 was lost?

A

Alarm window on board 2
RCP seal injection controllers (right 2 go dark)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How can you tell if NNN-D15 was lost?

A

Board 6 alarm pattern is across.

Hood spray indicator out

In unit 1 FWPT A steam valves will start closing, recirc valve will start opening. Trip ‘A’ MFP (IN UNIT ONE ONLY)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How can you tell if NNN-D16 was lost?

A

Board 6 alarm pattern is down.

one of the controllers next to hood spray

In unit 1 FWPT B steam valves will start closing, recirc valve will start opening. Trip ‘B’ MFP (IN UNIT ONE ONLY)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How can you tell if PNA or PNB was lost?

A

monitors on Board 5 on applicable channel

CREFAS/ CPIAS/ FBEVAS both trains actuate

(All class auxiliaries start) SP, EW, EC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How can you tell if PNC was lost?

A

‘C’ CPC monitor goes blank, No SESS or RU alarms

The pac-man for 3/4 of the core on Ovation on core mimic screen, you have to select on one of the ancillary screens because the screen we normally look at loses power.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How can you tell if PND was lost?

A

D’ CPC monitor goes blank
The anti-pac man for 1/4 the core on Ovation on core mimic screen, main screen we look at still available, we do lose other screens.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How can you tell if NKN-D42 was lost?

A

lose CHP’s
lose letdown
Lose EDP ‘A’ handswitch lights
NAN-S02 LC breaker lights lost
A Diesel Air Start SEIS light on

How well did you know this?
1
Not at all
2
3
4
5
Perfectly